K
–
R3
Module
K
‐
4
Compressor
Circuit
Operation
–
Dehumidifier
with
“Full
AC
with
No
Outdoor
Condenser”:
Piping
schematic
for
compressor
circuit
is
shown
on
Pic.
K.3
below.
When
a
demand
requires
the
compressor
to
operate,
the
following
sequence
occurs:
Once
blower
operation,
related
safeties
and
timers
are
confirmed
by
the
control
system,
the
pump
down
solenoid
valve
opens
and
once
pressure
stabilizes,
the
compressor
starts.
Reheat
valve
diverts
portion
of
hot
gas
into
the
reheat
coil.
Remainder
of
the
hot
gas
goes
through
pool
valve
into
AC
heat
exchanger
(evaporative
cooling
coil)
and/or
full
flow
pool
water
heat
exchanger.
Pool
valve
diverts
portion
of
hot
gas
into
full
flow
pool
water
heat
exchanger
or
evaporative
cooling
coil.
If
any
amount
of
heat
is
diverted
into
the
evaporative
cooling
coil:
o
R3
module
exhaust
fan
is
controlled
as
outdoor
condenser
fan:
its
speed
is
based
on
compressor
head
pressure
level
(see
Outdoor
Condenser
and
Fluid
Cooler
Operation
).
o
once
compressor
head
pressure
exceeds
the
pre
‐
set
level,
condensate
pump
is
engaged
–
air
moisture,
condensed
in
the
dehumidifier’s
evaporator
coil
and
collected
in
the
R3
module
drain
pan,
is
pumped
through
the
nozzle
manifold
and
sprayed
onto
the
evaporative
condenser
coil
to
increase
heat
rejection,
thus
maintaining
compressor
head
pressure.
Once
demand
for
the
compressor’s
operation
is
removed
(respective
call
is
satisfied),
the
pump
down
solenoid
valve
closes;
once
the
compressor
suction
pressure
reaches
the
pre
‐
set
pressure,
the
compressor
stops
Pic.
K.3
Summary of Contents for CLASSIC NE-002
Page 3: ...B Table of Content B 2 This page is left blank...
Page 10: ...C General Information OMM C S SL 01 C 7 February 2020 Pic C 4 B...
Page 17: ...D Layout and Components D 6 This page is left blank...
Page 21: ...E Sequence of Operation E 4 This page is left blank...
Page 25: ...F Interface and Communication F 4 This page is left blank...