D
–
Layout
and
Components
D
‐
2
Main
Blower
(1)
is
in
the
main
blower
compartment
next
to
the
Main
Electric
Panel
(2)
and
Compressor
Compartment
(3).
Min
Outdoor
Air
(OA)
Opening
(4)
is
optionally
equipped
with
a
motorized
damper
and
filter(s).
The
Manual
OA
Damper
(5)
is
usually
used
to
set
proper
amount
of
outdoor
air
intake.
Refrigeration
coils
‐
Evaporator
(7)
and
Reheat
(internal
condenser)
(8)
‐
are
located
directly
downstream
of
the
Main
Filter
Rack
(9).
o
Evaporator
Bypass
Damper
(10)
is
located
next
to
the
evaporator
coil.
It
helps
to
control
compressor
suction
pressure
by
adjusting
the
amount
of
air,
bypassing
the
evaporator.
Space
heater
(11)
location,
if
the
dehumidifier
is
equipped
with
one,
may
vary:
o
Hot
water
coil
is
usually
located
directly
downstream
of
the
reheat
coil;
o
Electric
heater
may
be
in
the
same
place
as
the
hot
water
coil
or
mounted
directly
on
the
dehumidifier’s
supply
air
duct
connection.
o
Gas
heater
(duct
heater
or
boiler
package)
normally
is
installed
externally,
however
some
models
could
have
duct
gas
heater
mounted
on
the
top
of
the
dehumidifier.
Compressor
(13),
Receiver
(14)
and
other
components
are
located
within
the
Compressor
Compartment
(3)
.
o
If
the
dehumidifier
has
the
standard
pool
water
heating
option,
the
compressor
circuit
includes
the
coaxial
pool
water
heat
exchanger
(15)
and
refrigeration
pool
valve.
o
If
the
dehumidifier
has
the
water
‐
cooled
air
conditioning
option
(equipped
with
fluid
cooler
or
connected
to
external
water
‐
cooling
source),
the
compressor
circuit
also
includes
the
plate
heat
exchanger
(16)).
Main
Electric
Panel
contains
Main
Control
Board
(17),
Operator
Panel
(18)
and
other
electrical
components.
Control
System
The
dehumidifier
control
system
is
composed
of
sensors,
spread
throughout
the
dehumidifier,
Main
Control
Board
,
Operator
Panel
and
other
electric
components,
located
in
the
Main
Electric
Panel.
Temperature
Sensors
(Pic.
D.2):
a)
Temperature
sensors
(thermistors)
are
used
to
monitor
various
temperatures
(air,
water,
compressor,
etc.);
b)
Combo
sensor
is
used
to
monitor
air
temperature
and
humidity.
Compressor
operation
is
monitored
with
pressure
sensors
(Pic.
D.3):
c)
Pressure
Transducers
(as
main
operational
control
and
safety)
and
d)
Pressure
Switches
(fast
‐
reacting
backup
safety).
Sensors
and
safeties
approximate
location
is
shown
on
Pic.
D.4
.
b
a
c
d
Pic.D.3
Pic.
D.2
Summary of Contents for CLASSIC NE-002
Page 3: ...B Table of Content B 2 This page is left blank...
Page 10: ...C General Information OMM C S SL 01 C 7 February 2020 Pic C 4 B...
Page 17: ...D Layout and Components D 6 This page is left blank...
Page 21: ...E Sequence of Operation E 4 This page is left blank...
Page 25: ...F Interface and Communication F 4 This page is left blank...