3.10  CR/42/24 CONTROL UNIT PROGRAMMING

With the control unit powered, release the gate, open it approx. 2 metres, then relock it. Press the PROG, 
button once; the DL8 LED will start flashing, indicating that the control unit has entered the programming phase.

The next section deals with the CR/42/24 control unit programming.
It is important to follow the programming step by step; in the event of errors during this stage, a new programming 
session must be performed, in which case the new data will replace the previous data.
To quit an incorrect programming session, switch the control unit off then on again.

Before proceeding with the programming, check that the system is equipped with all the electrical and safety devices 
(buttons, photocells, flashing lights, etc.) and that they are all connected. Ensure they all operate correctly, i.e.:

 All the indicator LEDs for the NC inputs (stop, photocell, limit switch) are lit;
 All the indicator LEDs for the NO inputs (open/close, pedestrian) are off.

In the event of faults, ascertain and remove the cause.

CAUTION:

 ANY UNUSED NORMALLY CLOSED (NC) INPUTS MUST BE JUMPERED.

3.10.1 PROGRAMMING THE WORK TIMES AND IMPACT FORCE SETTING MANUALLY

The deceleration point is set by the installer and can be cut out

Press the WORK button once to start the closure manoeuvre. The sliding gate will begin the closure manoeuvre 
with a starting thrust and will then decelerate and continue at a slow pace.
During slowing down, adjust the VELOCITA RALLENTAMENTO trimmer to set the force that will be applied 
during deceleration (in the event of impact with an obstacle).
Once the closure manoeuvre is complete and the FCC (closure limit switch) LED is off, press the LAVORO 
(

Operation

) button once: the gate will start opening.

During the opening manoeuvre, adjust the VELOCITA REGIME trimmer to set the force that will be applied 
during il normale funzioanmento (in the event of impact with an obstacle).

Before the gate completes the opening manoeuvre, press the LAVORO (

Operation

) button (we recommend 

doing this when it is 50 cm away from the end stop). This sets the desired deceleration start point, and the gate 
will start the deceleration phase.
N.B. If you wish to deactivate deceleration during normal operation cycles, skip this step and dip4 SW1 ON.

As soon as the gate has completed the opening manoeuvre, the work cycle is acquired, as is the deceleration 
point, if set. After a few seconds, the closure manoeuvre starts, and the programmed deceleration is applied.
When the gate reaches the closure limit switches (FCC LED off), the control unit automatically quits the 
programming phase and switches to standard operation mode.

CAUTION: If one or more parameters are altered, programming must be repeated 

from the beginning.

Page 12/16

3.10.2  GATE OPEN PAUSE TIME PROGRAMMING

With the control unit powered and the gate closed (closure limit switch  FCC - LED off), press the PROG, 
button once; the DL8 LED will start flashing, indicating that the card has entered the Programming phase.
Press the PAUSA (

Pause

) button once, keeping it pressed until the flashing light comes on; the control unit will 

start the gate open pause count, which is indicated by the light flashing intermittently.
Once the desired time has lapsed, press the PAUSA (

Pause

) button again; the control unit will automatically 

store the amount of time between the two times the PAUSA (

Pause

) button was pressed. It then quits the 

programming phase and switches to standard operation mode. If the PAUSA (

Pause

) button is not pressed a 

second time within 120 s, the control unit quits the programming, memorising the maximum time as 120 s.

ACTIVATING AUTOMATIC RECLOSURE (max time settable: 120 s)

With the control unit powered and the gate closed (closure limit switch  FCC - LED off), press the PROG button 
once; the DL8 LED will start flashing, indicating that the card has entered the programming phase.

Press the PAUSA (

Pause

) button and keep it pressed until the DL8 LED switches off.The control unit quits the 

programming phase and switches to standard operation mode.This operation deactivates the automatic 
reclosure function.

DEACTIVATING AUTOMATIC RECLOSURE

SIN

C

 1

96

5

M

E

R

C

U

R

IO

/5

2

4

A

  

 E

CONTROLS MODIFICATION 

(available starting from model A009-11, id. code on the micro)

It is possible to modify the functioning of the 22 and 23 inputs in this way:
- Input 23 functions as "START": with control unit off, press and hold keys "PROGR" and "WORK" simultaneously 

and apply power supply.

- Input 23 functions as "CLOSE only": with control unit off, press and hold keys "PROGR" and "PAUSE" 

simultaneously and apply power supply.

- Input 22 functions as "PEDESTRIAN": with control unit off, press and hold keys "WORK" and "PAUSE" 

simultaneously and apply power supply.

- Input 22 functions as "OPEN only": with control unit off, press and hold keys "PAUSE" and "WORK" and 

"PROGR" simultaneously and apply power supply.

Summary of Contents for MERCURIO 524A F

Page 1: ...ERCURIO 524A F SR 24 85 24AF KIT WITH ENCODER FOR SLIDING GATES UP TO 500 kg 24Vdc CAUTION READ THIS MANUAL CAREFULLY BEFORE MAKING ANY CONNECTIONS AND KEEP FOR FUTURE REFERENCE MERCURIO 524A H SR 24 84 24A MOTOR WITH CONTROL UNIT FOR SLIDING GATES UP TO 500 kg 24Vdc ...

Page 2: ...C Electromagnetic compatibility 2004 108 EEC General applicable standards Electrical safety IEC EN60335 1 IEC EN60335 2 103 Electromagnetic compatibility emissions IEC EN61000 6 3 Electromagnetic compatibility immunity IEC EN61000 6 1 Apart from the legislation mentioned above you are also reminded to comply with the following standards during the installation phase General applicable standards Sa...

Page 3: ... of the system choosing one with a gap of at least 3 mm between the contacts Or alternatively use a 10Amagnetothermic switch 2 When making the connections using any type of connector ensure the system is disconnected from the power supply i e that the main switch is in the open position 0 symbol The control unit in particular must never be connected to the power supply either during the wiring up ...

Page 4: ...THE BASE PLATE 35 mm 2 2A Screw the two nuts onto the bolts until they are positioned 35 mm from the end of the thread Fit the J bolts through the holes in the base plate Screw the other two nuts onto the J bolts without tightening 2 2B Dig a hole and place the base plate fastened to the bolts inside it along with the cable carrier hose Position the base plate at the heights specified fastening it...

Page 5: ...the 2 nuts without tightening them completely These bolts must not be secured until the tooth rack is in its final position 2 5 RELEASING THE MOTOR 2 4 B Cut small holes in the rubber seals so that they grip each of the cables properly If this operation is not carried out and insects get inside the unit a short circuit may occur causing irreparable damage to the ECU Fit the release key into the lo...

Page 6: ...NSTALLATION 2 6 A CAUTION check that the pinion engages with the tooth rack along the entire width of the tooth NO YES PINION TOOTH RACK PINION TOOTH RACK M 14 STEEL TOOTH RACK INSTALLATION 2 6 C Lay the 2 m tooth rack bars in a line so that the entire distance of the gate motor sliding plates is covered if necessary cut the last bar to size Weld the tooth rack to a steel corner piece dimensions 4...

Page 7: ...ical end stops during opening and closure If this occurs the FLAP COULD GET BROKEN during the release operation Because of seasonal temperature differences we recommend you check this in both summer and winter CAUTION For safety reasons an end stop must be fitted for both the closure and opening movements 2 8 DEFINITIVE MOTOR FASTENING 2 8 A Tighten the nuts on the J bolts fully Place the lower pl...

Page 8: ...e open indicator light output 24Vdc max 50mA 10 9 19 PHOTOCELL FOR CLOSURE Input for photocell active only in closure NC contact in closure the gate reverses the motion SLOW DOWN SPEED Trimmer for motor speed adjustment during slow down phase BLACK do not use YELLOW do not use 24 25 24 25 DL9 Batterie 12Vdc 1 2Ah OPTIONAL SOG 4A Connector for any SOG 4A receiver cards ENCODER Connector for encoder...

Page 9: ...essed Open Close button pressed Gate close or in intermediate position NC contact Gate completely closed NO contact Gate completely open NO contact Photocell obscured obstacle present Stop button pressed Pedestrian button in normal status Open Close button in normal status DL8 Programming Test Flashing light to show programming mode has been accessed High frequency flashing light to indicate fault...

Page 10: ...f the photocell is obscured during opening the gate stops moving but starts again as soon as the photocell is clear if the photocell is obscured during closure the gate will stop moving and then start opening again Force limitation activated in the event of an impact with an obstacle whether during opening or closure an encoder system detects the impact stops the gate and then reverses it by 10cm ...

Page 11: ... failure The batteries have to be connected in series see Picture aside the positive cable has to be connected to the clamp 2 BATTERY and the negative cable to the clamp 1 BATTERY 3 7 MOTOR WORKING WITHOUT ENCODER The control panel CR 42 24 has been conceived to work also without ENCODER therefore can be used also with other kind of motors 24Vdc The control panel can be enabled to work without enc...

Page 12: ...uvre the work cycle is acquired as is the deceleration point if set After a few seconds the closure manoeuvre starts and the programmed deceleration is applied When the gate reaches the closure limit switches FCC LED off the control unit automatically quits the programming phase and switches to standard operation mode CAUTION If one or more parameters are altered programming must be repeated from ...

Page 13: ... MICROSWITCH CONFIGURATION FOR OG 02AND OG 04 MINI TRANSMITTERS ONLY These instructions only apply if the OG 02 and OG 04 series microswitchoperated mini transmitters are fitted Before performing the code learning procedure on the receiver the factory set configuration of the microswitches must be modified to prevent unwanted commands CAUTION before proceeding with the mini transmitter programming...

Page 14: ...AX RX TX TX RX RX RX TX TX NO OK h MIN 5 3 INSTALLATION CABLE ROUTING HOLE RECEIVER TRANSMITTER RELAY OUTPUT THE CONTACT POSITION REFERS TO WHEN THE RECEIVER IS ENERGIZED POWER SUPPLY 5 2AThe receiver must not be exposed to direct sunlight recommended height from ground 50 cm 5 2 C If two pairs of photocells are installed position the transmitters on opposite sides NO OK LED RECEIVER TRANSMITTER 5...

Page 15: ...ULBS WITH MIN SPECIFICATIONS 24V 25W E14 2 x 0 75 mm POWER SUPPLY RG58 ANTENNA CS 07 SR12 07 OPTIONAL CABLE CONNECTIONS 230 Vac OK CAUTION WE RECOMMEND THAT THE POWER SUPPLY CABLE BE POSITIONED INSIDE A CONDUIT WHICH IS NOT ACCESSIBLE BY THE USER IF ON THE OTHER HAND THERE ARE ANYACCESSIBLE PARTS THESE MUST BE DOUBLY INSULATED FOR THE USER S PROTECTION A CABLE CLAMP MUSTALSO BE USED TO PREVENT THE...

Page 16: ...e other safety systems compliant with regulations in force e g sensitive edges must be adopted This is extremely important as THE INSTALLER IS LIABLE FOR THE SYSTEM AND FOR ENSURING ITS OPERATION COMPLIES WITH LEGAL PROVISIONS The remote control range is reduced Unsuitable antenna connection Check that the antenna is connected correctly to terminals 24 and 25 External antenna required To permit ma...

Reviews: