Dear Fitter,
Should, against expectations, reasons for complaints
regarding this unit arise, we ask you to please describe
the error as accurately as possible to allow for spee-
dy repair processing.
For every returned control please always include the
sensors.
Error messages in the display indicate:
ERROR 1:
Overtemperature fuse
F I defective
ERROR 2:
Internal error of the control
(return control)
ERROR 3:
Break in sensor line F I
ERROR 4:
Short circuit of line F I
ERROR 5:
Short circuit of line F II
ERROR 6:
Interruption of line F II
Installation instructions for trained electricians only
5
Tests
An authorized electrician must carry out the tests.
WARNING - Electric shock:
The following tests are carried out with the
supply voltage switched on.
1. Test contact to ground terminal.
2. Test the safety shutdown with the line to the tem-
perature sensor / fuse interrupted.
-
The line has to be loosened at the sensor, so that
the sensor line is included in the test.
-
When loosening the white or the red sensor line
the heating system has to turn off by itself.
3
Test the phase interconnection for sauna opera-
tion L1, L2, L3 to U,V,W.
4. With connected, optional additional power unit:
-
Checking the control lines St1, St2 and St3
-
Check the maximum permitted heating capacity of
9.0 kW at the power supply unit and for 9 kW or
21kW respectively at the optional power unit.