27
Installation instructions for trained electricians only
3
Installing temperature sensor F I
with overtemperature fuse
Figures
4 6
Fit the temperature sensor F I with overtemperature fuse
in the center of the sauna cabin about 15 cm below the
ceiling, above the heating system, or in accordance
with the cabin manufacturer's specifications.
Connect the sensor F I with the attached
150 °C temperature-resistant line or an equivalent
temperature-resistant line only.
On the outside of the sauna cabin, the temperature-
resistant connecting line can be extended with custo-
mary lines.
CAUTION - Double insulation is required:
The sensor lines have to be run separately
to other circuit and control lines.
Single insulated lines have to be protected
with a pipe (double insulation).
1. Run four-pin line
5
to mounting site of sensor FI
4
in the cabin wall and fix in position with wiring
clips.
2. Separate two half shells
1
of the sensor F I and
connect four terminals of the temperature-resis-
tant connection line according to the circuit dia-
gram (figure
6
).
3. Conduct tests according to the chapter “Tests”
4. Insert round adapter plate
2
with the connections
crosswise in the half shells
1
, close half shells
1
and fasten with the two, 9 mm long, Philips
head screws
3
.
Check for secure lock of sensor F I.
5. Fix sensor F I
4
with two wood screws to the
cabin wall in alignment with the heater, keeping
a distance of 15 cm to the ceiling, or fasten with
two wood screws
6
to the cabin wall according
to the cabin manufacturer's specifications.
4
Installing the temperature sensor
F II
Figures
5 6
Install the bench sensor in the sauna cabin about 15
cm below the ceiling and opposite of the heating sys-
tem.
The bench sensor with its overtemperature fuse may
only be connected with the attached 150 °C tempe-
rature-resistant connecting line or an equivalent tem-
perature-resistant line.
On the outside of the sauna cabin, the temperature-
resistant connecting line can be extended with custo-
mary lines.
CAUTION - Double insulation is required:
The sensor lines have to be run separately
to other circuit and control lines.
Single insulated lines have to be protected
with a pipe (double insulation).
1. Run line
5
to bench sensor installation site
4
in the sauna wall and fix in position with wiring
clips.
2. Separate two half shells
1
of bench sensor
4
and connect two terminals of the up to 150° C
temperature-resistant line according to the circuit
diagram
6
.
3. Conduct tests according to the chapter “Tests”.
4. Insert round adaptor plate
2
with the connections
crosswise in the half shells
1
, close half shells
1
and fasten with the two, 9 mm long, Philips
head screws
3
.
Check for secure fit of bench sensor
4
.
5. Fix bench sensor
4
to the cabin wall opposite of
the heating system with two wood screws
6
keeping a distance of 15 cm to the ceiling.