www.sentera.eu
MIW-MCS-1-LCD-EN-000 - 20 / 07 / 2016
16 - 33
USING PREDEFINED TEMPLATES
See table
Table
below to know about the available templates that pre-define the
device functionality.
Device functionality
Parameters
Predefined templates
Free
Temperature
cool
Temperature
heat
Relative
humidity
CO
2
Air quality
Differential
pressure
Temperature
and CO
2
Differential
pressure and
temperature
Control range (T1)
0—40°C
0—40°C
N/A
N/A
N/A
N/A
0—40°C
0—40°C
0—40°C
Off level (T1)
-10°C
40°C
N/A
N/A
N/A
N/A
-10°C
-10°C
-10°C
Setpoint (T1)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
20°C
N/A
Control range (T2)
0—40°C
0—40°C
N/A
N/A
N/A
N/A
N/A
N/A
0—40°C
Off level (T2)
0°C
40°C
N/A
N/A
N/A
N/A
N/A
N/A
-10°C
Setpoint (T2)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Control range (Ail)
N/A
N/A 20—80 % rH 0—2.000 ppm 0—2.000 ppm
0—2.000 Pa 0—2.000 ppm
0—2.000 Pa
0—10.000
units
Off level (Ail)
N/A
N/A
20 % rH
0 ppm
0 ppm
0 Pa
0 ppm
0 Pa
N/A
Setpoint (Ail)
N/A
N/A
N/A
N/A
N/A
N/A
1000 ppm
N/A 5.000 units
Control range
(Ai2)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
0—10.000
units
Off level (Ai2)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Setpoint (Ai2)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A 5.000 units
Analog output
function (Aol)
Linear
Linear
Linear
Linear
Linear
Linear
Controlled
Controlled
Controlled
Analog output
mode (Aol)
Cool
Heat
0—10 VDC
0—10 VDC
0—10 VDC
10—0 VDC
N/A
N/A
N/A
Assigned normal
input (Aol)
T1
T1
Ai1
Ai1
Ai1
Ai1
T1
Ai1
T1
Assigned high
priority input (Aol)
N/A
N/A
N/A
N/A
N/A
N/A
Ai1
T1
Ai1
Analog output
function (Ao2)
Linear
Linear
N/A
N/A
N/A
N/A
Linear
Linear
Controlled
Analog output
mode (Ao2)
Cool
Heat
N/A
N/A
N/A
N/A
0—10 VDC
Cool
N/A
Assigned normal
input (Ao2)
T2
T2
N/A
N/A
N/A
N/A
Ai1
T1
T2
Assigned high
priority input
(Ao2)
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Ai2
MCS-1-LCD
MULTIFUNCTIONAL LOGIC
CONTROLLER