HOLDING REGISTERS
Data type
Description
Data
Default
Values
74
Assign high priority input to
analogue output (Ao2)
unsigned int.
Assigns high priority analogue or
temperature input to analogue output
Ao2.
Active only if not in relation and
controlled output is selected.
0—3
2
0 =
1 =
2 =
3 =
T1
T2
Ai1
Ai2
75
Time to maximum output
(Ao2)
unsigned int.
Time for the output to rise to maximum
value.
Active only if control function is
selected.
0—100 s
60 s
60 =
60 s
76
Kp value (Ao2)
unsigned int.
Proportional gain value for Ao2.
Active only if a PID function is selected.
1—1.000
10
10 =
1,0 gain
77
Ti value (Ao2)
unsigned int.
Integration period value for Ao2.
Active only if a PID function is selected.
1—6.000
100
1 =
100 =
0,1 s
10 s
78
Td value (Ao2)
unsigned int.
Derivative period value for Ao2.
Active only if a PID function is selected.
0—6.000
10
0 =
10 =
0 s
1 s
79
Assigned input to relay 1
unsigned int.
Assigns a relation to analogue or digital
input of relay 1
0—8
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
Not in use
Di1
Di2
Di3
Di4
T1
T2
Ai1
Ai2
80
Assigned input to relay 2
unsigned int.
Assign relation to analogue or digital
input of relay 2
0—8
0
0 =
1 =
2 =
3 =
4 =
5 =
6 =
7 =
8 =
Not in use
Di1
Di2
Di3
Di4
T1
T2
Ai1
Ai2
81
Hour
unsigned int.
Current hour
0—23
82
Minutes
unsigned int.
Current minutes
0—59
83
Seconds
unsigned int.
Current seconds
0—59
84
Date
unsigned int.
Current date and month
1—31
85
Month
unsigned int.
Current month
1—12
86
Year
unsigned int.
Current year
2000—2099
87
Day of week
unsigned int.
Current day of the week
0—6
0 =
1 =
2 =
3 =
4 =
5 =
6 =
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
88
Day of year
unsigned int.
Current day of year
1—366
89
Autotune (Ao1)
unsigned int.
Starts autotune in PID control for
analogue output Ao1
0—1
0
0 =
1 =
In progress (start autotune)
Stop
90
Autotune (Ao2)
unsigned int.
Starts autotune in PID control for
analogue output Ao2
0—1
0
0 =
1 =
In progress (start autotune)
Stop
91
Analogue output override
value (Ao1)
signed int.
Override value for analogue output
Ao1.
Active only if holding registers 7
and 8 are set to 1.
0—1.000
0
0 =
1.000 =
0 VDC
10,00 VDC
92
Analogue output override
value (Ao2)
signed int.
Override value for analogue output
Ao2.
Active only if holding registers 7
and 8 are set to 1.
0—1.000
0
0 =
1.000 =
0 VDC
10,00 VDC
93-100