www.sentera.eu
MIW-MCS-1-LCD-EN-000 - 20 / 07 / 2016
28 - 33
MODBUS REGISTER MAPS
INPUT REGISTERS
Data type
Description
Data
Values
1
Temperature level (T1)
signed int.
Temperature level (T1)
-300—700
500 =
50,0°C
2
Temperature level (T2)
signed int.
Temperature level (T2)
-300—700
500 =
50,0°C
3
Analogue input level (Ai1)
signed int.
Analogue input level (Ai1)
0—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
4
Analogue input level (Ai2)
ttsigned int.
Analogue input level (Ai2)
0—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
5
Digital input status (Di1)
signed int.
Digital input status (Di1) - active / inactive
0—1
0 =
1 =
inactive
active
6
Digital input status (Di2)
signed int.
Digital input status (Di2) - active / inactive
0—1
0 =
1 =
inactive
active
7
Digital input status (Di3)
signed int.
Digital input status (Di3) - active / inactive
0—1
0 =
1 =
inactive
active
8
Digital input status (Di4)
signed int.
Digital input status (Di4) - active / inactive
0—1
0 =
1 =
inactive
active
9-10
Reserved, returns 0
11
Analogue output value (Ao1)
signed int.
Value of the analogue output (Ao1) - 0—10 VDC
0—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
12
Analogue output value (Ao2)
signed int.
Value of the analogue output (Ao2) - 0—10 VDC
0—1.000
300 =
300 =
3,0 VDC (30 %)
6 mA (30 %)
13
Relay 1 status
signed int.
Relay 1 status.
When it is
NO
, the contact between
COM1 and NO1 is closed.
0—1
0 =
1 =
NC
NO
14
Relay 2 status
signed int.
Relay 2 status.
When it is
NO
, the contact between
COM1 and NO1 is closed.
0—1
0 =
1 =
NC
NO
15
Current year
unsigned int.
Current year
2000—2099
16
Current month
unsigned int.
Current month
1—12
1 =
12 =
January
December
17
Current day
unsigned int.
Current day
1—31
18
Current hour
unsigned int.
Current hour
0—23
19
Current minutes
unsigned int.
Current minutes
0—59
20
Current seconds
unsigned int.
Current seconds
0—59
21
Temperature input sensor range (T1)
signed int.
Selected temperature input sensor range (T1),
calculated from holding registers values
-300—700
0—500 =
0—50,0 °C
22
Temperature input control range (T1)
signed int.
Selected temperature input control range (T1),
calculated from holding registers values
-300—700
0—500 =
0—50,0 °C
23
Off level for temperature input (T1)
signed int.
Selected off level for temperature input (T1)
-200—600
500 =
50,0 °C
24
Setpoint for temperature input (T1)
signed int.
Selected setpoint for temperature input (T1)
-200—600
500 =
50,0 °C
25
Hysteresis for temperature input (T1)
signed int.
Selected hysteresis for temperature input (T1)
5, 10, 15,
20, 25, 30
5 =
10 =
15 =
20 =
25 =
30 =
0,5 °C
1,0 °C
1,5 °C
2,0 °C
2,5 °C
3,0 °C
26
Sensor type (T1)
unsigned int.
Current sensor type connected to the input (T1)
0—1
0 =
1 =
PT500
PT1000
27
Temperature input sensor range (T2)
signed int.
Selected temperature input sensor range (T2),
calculated from holding registers values
-300—700
0—500 =
0—50,0 °C
28
Temperature input control range (T2)
signed int.
Selected temperature input control range (T2),
calculated from holding registers values
-300—700
0—500 =
0—50,0 °C
29
Off level for temperature input (T2)
signed int.
Selected off level for temperature input (T2)
-200—600
500 =
50,0 °C
30
Setpoint for temperature input (T2)
signed int.
Selected setpoint for temperature input (T2)
-200—600
500 =
50,0 °C
31
Hysteresis for temperature input (T2)
signed int.
Selected hysteresis for temperature input (T2)
5, 10, 15,
20, 25, 30
5 =
10 =
15 =
20 =
25 =
30 =
0,5 °C
1,0 °C
1,5 °C
2,0 °C
2,5 °C
3,0 °C
32
Sensor type (T2)
unsigned int.
Current sensor type connected to the input (T2)
0—1
0 =
1 =
PT500
PT1000
33
Analogue input sensor range (Ai1)
unsigned int.
Selected analogue input sensor range (Ai1),
calculated from holding registers values
0—1.000
0—1.000
0—10 VDC
34
Analogue input control range (Ai1)
unsigned int.
Selected analogue input control range (Ai1),
calculated from holding registers values
0—1.000
0—1.000
0—10 VDC
MCS-1-LCD
MULTIFUNCTIONAL LOGIC
CONTROLLER