Setup
Page 34
UltraWave Product Guide
3. Download the configuration changes to the receiver unit.
4. In the Transmitter Serial Number field, enter the serial number for the paired transmitter unit.
(If the receiver is communicating with the transmitter unit, click the serial number button beside
the Transmitter Serial Number field to enter the Tx serial number.)
5. If desired, select the Fast Response Enable checkbox to increase the speed at which the
Ultrawave sensor reports a microwave alarm.
6. Specify the Thresholds (Crawling Target and Upright Target).
Use the UCM Height Calc tool to determine the optimal detection Thresholds.
The Thresholds can be adjusted later, if required, during the system verification tests.
Figure 31 UCM Config tab (receiver unit)
Note
Fast Response Enable is a parameter that is used to bypass the
sensor’s advanced signal processing algorithms. When Fast
Response is enabled, UltraWave functions like a classic analog
microwave sensor. An alarm is triggered when the microwave signal
exceeds the Threshold setting. The Fast Response channel provides
early alarm notification, but can also cause an increase in the
sensor’s nuisance alarm rate (NAR). Fast Response is intended for
use in high-security applications that include a sterile zone. However,
Fast Response should NOT be used in Sally Port areas.
set the Locale (region of operation)
set the Frequency Pair
enter the Transmitter Serial Number
open the Height Calculator tool
select the Thresholds
(or select it by clicking the button)
Fast Response Enable is an advanced
parameter for high security applications
set the receiver’s network address
update the receiver’s firmware