55
Chapter 3: Operation
Voice Status Report and Touch-Tone Commands
The IMS-1000 is capable of delivering a spoken status report when called via telephone. The status
report can provide information on both environmental conditions and IP alarms.
Sample Status Report
To receive a status report, call the unit. The unit will answer and begin speaking and request your
User Code
. If the unit receives a valid User Code it will continue with several menu options. A
sample of the main menu is shown below:
Hello, this is the IMS-1000 - "this the ABC Federal Savings Bank at 1040 Chestnut Street"
(custom voice message)
Enter your User code. {valid code is received}
No alarms exist.
For an Alarm Summary Report, Press 1
To listen to an Environmental Status Report, press 2.
To listen to an IP status report, Press 3.
To play or record a voice message, Press 4.
To control the Relay Output, Press 5.
To repeat this menu, Press 0.
If the caller had selected option 1 they would hear an environmental status report. The alarm sum-
mary only reports on inputs and IP alarms that are currently beyond their limits, or are in an alarm
condition. A sample of an environmental status report is listed below. Items in italics are custom
messages recorded by the user.
Channel 1,
temperature in the server room
, is 76.4 degrees Fahrenheit, normal
Channel 2,
temperature in rack B
, is 82.7 degrees Fahrenheit, too high
Channel 3,
humidity in the server room
, is 33.9%, normal
Channel 6,
water under server room floor
, normal
Channel 7,
smoke alarm in the server room
, normal
The power is ON
The battery is 100%, normal
Voice Alarm Dialout
The IMS-1000 can call and deliver an alarm message in spoken English. After dialing, the unit
will begin speaking “IMS-1000 Alarm Message, Press any key to continue.” If the unit receives a
touch-tone, it will recite the alarm message. When it finishes speaking the message it will request
acknowledgement. A sample Voice Alarm call is shown below:
“Sensaphone Alarm Message, press any key to continue”
“Sensaphone Alarm Message, press any key to continue” {call is answered and a 5 is pressed}
“IMS-1000 Alarm Message. The temperature is High
at the IT Dept of XYZ Company
.”
“Channel 1,
temperature in the server room
, is 81.5 Degrees Fahrenheit”
“Level crossed limit of 80 Degrees Fahrenheit at 7:45PM.”
"To repeat press *"
Summary of Contents for IMS-1000
Page 1: ...IMS 1000 User s Manual Version 1 4 SENSAPHONE...
Page 109: ...Test Log...
Page 110: ......