Chapter 2: Configuration
35
: User Profile
Fig. 5
Username:
The Username is required to login to the system when security is enabled. The
Username can be up to 48 characters.
Password:
The Password is required to login to the system when security is enabled. The Password
can be up to 48 characters.
Enable/Disable
: If a profile is Disabled the user will not be able to login or access a voice status
report.
User Code:
The User Code is required to acknowledge alarms over the telephone or to call-in for a
voice status report. The User Code must be 4 digits.
Access Level
: This determines what registered Users can see and/or change when logged into
the system. There are three Access Levels: Status, User, and Administrator. The Status and User
levels are both read-only. The Status level can only see the Summary and Channels screens. The
User level can see everything, can acknowledge alarms and switch the output but cannot make any
changes. The Administrator can read or write all programming parameters.
Deleting a Profile
To delete a profile, click on the
User Profiles
button at the top of the page and select one or more
profiles by clicking in the boxes next to the profile names, then click the
Delete
button.
Contacts
The Contacts are the actual telephone numbers, e-mail addresses, pager numbers, etc… that the
IMS-1000 will contact when an alarm occurs. You can have up to 4 Contacts per User Profile. Only
Contacts which are Enabled when the alarm occurs, will be contacted. E–mail and SNMP contacts
will be sent immediately, telephone calls will be dialed in order.
: Contact Setup Screen
Fig. 6
Enter a Name which describes the contact, like “Jim’s Cell,” “Acme Inc. Fax,” or “Jim at home.”