7
SENS IQ Technical Manual
Service hotline: 1.800.742.2326
1.303.678.7500
Parameter Code Value
Parameter Code
Value
Nominal
DC output
voltage
012
024
048
120
240
12 volts nominal
24 volts
48 volts
110-120 volts
220-240 volts
Agency
marks
L
G
UL & C-UL listed (60 Hz input units)
UL & C-UL CE marked (50/60 Hz input units)
Rated
output
current
006
012
016
025
035
050
6 amps
12
16
25
35
50
Feature
package
511
512
514
534
Filtered package
- Standard input breaker
Eliminator package
- Adds battery eliminator output filter to 511
Eliminator Plus package
- Adds reverse polarity diode and
blocking diode to 512
Extreme package
- Adds18-25K AIC input breaker and input
inrush limiter to 514
AC input,
single
phase
T
P
3
S
8
4
V
120/208/240 V, 60 Hz
120/208/240 V, 50/60 Hz
208 V, 60 Hz (> 3.4 KW o/p)
240 V, 60 Hz (> 3.4 KW o/p)
480 V, 60 Hz
230, 50/60 (> 3.4 KW o/p)
400 VAC, 50/60 Hz
Alarm
relay and
data com-
munications
package
A
B
C
K
L
M
N
Single Form C summary alarm relay
Extended Individual Form C relays (AC fail, charger fail, low
battery volts, high battery volts, ground fault, end of discharge,
battery check)
Standard Individual Form C relays (AC fail, charger fail, low
battery volts, high battery volts, ground fault)
CommsGenius Load Share* + Standard Alarms
CommsGenius Load Share*
CommsGenius Modbus*
CommsGenius Modbus* + Standard Alarms
*See CommsGenius User Manual for more information
Special
option
E
R
OSHPD labeled (California Special Seismic Cert Pre-Approval)
Rack mount
5.1
Lifting
5
MECHANICAL INSTALLATION
The charger is designed to be lifted from the bottom by pallet jack or lift truck.
5.2
Charger Mounting Options
The charger is designed to mount on a wall using
wall mount flanges on the sides of the chassis.
See
drawings at back of manual
for details on mounting configurations. Do not mount the charger in
locations subject to high vibration. Do not mount the charger directly to the frame of an engine or
generator set.
5.3 Ventilation
The charger is designed to be convection cooled. Required clearances around the unit for proper cooling
are 6 inches on the top and 4 inches on the bottom.
5.4 Environmental
Considerations
The charger should be installed in a sheltered area, protected from rain and snow. The suggested
operating temperature range is –20°C/-4°F to +50°C/122°F, but the charger will operate safely outside of
this range. The charger is rated for –40°C/-40°F for black/cold start, and once it self heats to –20°C/-4°F
is guaranteed to meet all published specifications. The charger thermal limiter reduces output current to
prevent over-heating when ambient temperature is too high.
4 MODEL
NUMBER
CONFIGURATION
IQ
Nominal DC output
Rated output current
AC
Agency
Feature package
Alarm Special Option
Q
0
4
8
0
3
5
T
L
5
1
4
A
R
A
C
B
D
E
F
A
C
B
D
E
F
G
G