SENS IQ Technical Manual
36
Service Hotline: 1.800.742.2326
1.303.678.7500
Figure 19: Troubleshooting flowchart for GROUND FAULT alarm
TWO CHARGERS
CONNECTED IN
PARALLEL?
REMOVE LEAKAGE CURRENT
OR LOWER/DISABLE GROUND
FAULT SENSITIVITY
ALARM STILL
PRESENT?
END
START
Y
N
Y
N
GROUND FAULT DUE TO
BLOCKING DIODE (SEE
COMMSGENIUS USER MANU-
AL). LOWER OR DISABLE
GROUND FAULT SENSITIVITY.
N
CONTACT CUSTOMER
SERVICE
END
Y
CHARGER BLOCK-
ING DIODE AND
POSITIVE GROUND
FAULTALARM
PRESENT?
N
Y
COMMSGENIUS
LOAD-SHARE
CABLE CON-
NECTED?
GROUND FAULT LIKELY FALSE.
CONNECT COMMSGENIUS
LOAD-SHARE CABLE TO ENSURE
PROPER PARALLEL OPERATION.
Y
Y
END
N
LEAKAGE
CURRENT
PRESENT?
N
Y
N
ALARM STILL
PRESENT?
ALARM STILL
PRESENT?