background image

TECHNICAL SPECIFICATIONS

STANDARDS

EN61000-6-4

 

Electromagnetic emissions, industrial environment.

EN61000-6-2

 

Electromagnetic immunity, industrial environment.

EN61010-1 

Safety

Note for UL:

 use in environments with pollution degree 2. The power supply unit must be 

class 2. Install a fuse with a MAX capacity of 2.5 A near the module.

INSULATION

ENVIRONMENTAL  

CONDITIONS

T

emperature

:                       -20 – + 65°C (-10 - +60 °C UL) 

Humidity

:                               30%– 90% non condensing.

Altitude:                            

up to 2000 m above sea level 

Storage temperature:

 -20    + 85° 

Protection degree:           

IP20.

ASSEMBLY

IEC EN60715, 35mm DIN rail in vertical position.

CONNECTIONS

3-way removable screw terminals, 5mm and 10mm pitch

Rear connector IDC10 for DIN bar 46277

front micro USB

POWER SUPPLY

Voltage: 10 – 40 Vdc; 19 – 28 Vac ; 50 – 60 Hz

Absorption: Typical: 1.5 W @ 24Vdc, Max: 2.5 W

SERIAL COM.

RS485, 1200 – 115200 Baud - RS232, 2400 Baud, Address:01, Parity: NO, Data: 8 bit; 

Stop bit:1.

PROTOCOL

Modbus-RTU

OVERVOLTAGE 

CATEGORY

II (up to 300 V)

RETRANSMITTED 

INPUT/OUTPUT

Voltage input

:        Up to 500 Vac, frequency: from 35 to 75 Hz

Current input

:        Rated capacity: 5 Arms, Max Crest factor: 3

Maximum current: 

15 A, Frequency: from 35 to 75 Hz

Class/Base Prec.

:  Voltmeter: 0.5%: Ammeter: 0.5%; Wattmeter: 0.5% (active power)

ANALOGUE 

OUTPUT

Voltage output

:                      0 - 10 Vdc, 0..5 Vdc, minimum load resistance: 2 k Ω

Current output:               

       0 - 20 , 4..20 mA, max load resistance: 500 Ω

Retransmission error:            

0.1% of maximum field

DIGITAL OUT-

PUTS FOR 

ENERGY PULSE 

COUNTER

Type

:                 0 – 20 Passive (must be powered), R > 480 Ω

Capacity:           

50 mA

Insulation:         

1500 Vpeak

Terminals:          1

 and 6 ( common with GND analogue output)

3/8

WARNING

the maximum working voltage between any 

terminal and ground must be less than 50 

Vac / 75Vdc (input excluded).

Communication

Power

Supply

Input

Analog

Output

3750 V

~

10..40 Vdc / 19..28 Vac

mA / V

0..500 Vac
5 Arms

RS485

1500 V

~

PRODUCT DESCRIPTION

The Z203-2 is a complete single-phase network analyzer, suitable for voltage ranges up to 500 Vac, with currents 

up to 5 A (from 35 Hz to 75 Hz). The instrument can supply all the following electrical quantities: Vrms, Irms, Watt, 

Var, Frequency, Energy, Cos

ɸ

. The measurements are made available for reading via serial communication both 

in floating point format and normalized (except for energy).  By setting the Dip Switches or the Modbus registers, 

the analogue retransmission of any of the Vrms, Irms, Watt, Var, Frequency and Cos

ɸ

 quantities is possible. 

USB

Summary of Contents for Z203-2

Page 1: ...single phase network analyzer SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and configuration software visit www seneca i...

Page 2: ...seneca it products z203 2 Important Obstructing ventilation slots with any object is prohibited Installing the module next to devices that generate heat is prohibited Electrical and electronic waste...

Page 3: ...factor 3 Maximum current 15 A Frequency from 35 to 75 Hz Class Base Prec Voltmeter 0 5 Ammeter 0 5 Wattmeter 0 5 active power ANALOGUE OUTPUT Voltage output 0 10 Vdc 0 5 Vdc minimum load resistance 2...

Page 4: ...ional to the full scale value of the measured quantity For example if the retransmitted signal is in current 4 20 mA and the quantity to retransmit the voltage Vrms we will have that 4 mA will corresp...

Page 5: ...BAUD RATE 19200 38400 57600 1 ADDRESS 2 63 From EEPROM 5 8 DIP Switch status SW2 POSITION DESCRIPTION 1 2 3 4 5 6 7 8 Network frequency 50 Hz NETWORK NOMINAL FREQUENCY SELECTION 50 60 Hz Network frequ...

Page 6: ...nnectors are polarized 2 To secure the module to the DIN rail tighten the two hooks on the side of the IDC10 rear connector USB PORT The module is designed to arrange data according to the modes defin...

Page 7: ...Connection cable signal protection shield recom mended Retransmitted input output The module accepts an input voltage up to 500 Vac maximum Provide the input voltage to terminals 10 and 12 and connect...

Page 8: ...tings procedures refer to the USER MANUAL downloadable from www seneca it products z203 2 ATTENTION The upper power supply limits must not be exceeded as this might cause serious damage to the module...