PROGRAMMING

For the product programming and/or configuration tools, go to.seneca.it.

During initial programming, the EEPROM (SW1..8 IN OFF position) default settings that are originally programmed 

as follows, can be used: 

Address = 001, BAUD RATE = 38400, PARITY = none, BIT NUMBER = 8, STOP BIT = 1.

The module can also be programmed through the front connector (USB) and making sure you set the following 

parameters for the connection: Address = 001, Baud rate = 2400, PARITY = none, STOP BIT = 1. 

The USB communication port behaves exactly like that of the RS485 bus except for the communication 

parameters as already described. It also has priority over the RS485 port and is closed after about 15 seconds’ 

inactivity.

SERIAL INTERFACE

For detailed information on the RS485 serial interface, refer to the documentation on the www.seneca.it site, in the 

Products / Z-PC Series / MODBUS TUTORIAL section.

OPERATING LOGIC

The module provides, in the appropriate MODBUS registers, the values of the following electrical quantities: Vrms, 

Irms, Watt, Var, Frequency, Energy, Cos

ɸ

Except for energy, these measurements are available both in floating point format and normalized between 0 - 

+10000 (0 - +10000 for absolute values of VAR and cosΦ, 350..750 for frequencies between 35.0 Hz and 75.0 

Hz). The module retransmits as output, as a current or voltage signal, one of the previous quantities chosen by 

the user (excluding energy). The range of the retransmitted output is proportional to the full scale value of the 

measured quantity. For example, if the retransmitted signal is in current 4 - 20 mA and the quantity to retransmit 

the voltage Vrms, we will have that 4 mA will correspond to 0 V, and 20 mA will correspond to 500 V, this being the 

full scale for rms voltages.

You can also choose retransmission scaling: 100%, 50 % or 25 %. Getting back to the previous example but 

setting a 50% retransmission scaling, 4 mA will correspond to 0 V and 20 mA will correspond to 250 V. The 

retransmission values saturate at about 11 V for  voltage outputs and at about 21 mA for current outputs.

At start-up the appropriate calibration coefficients are taken (depending on the choice of 50 or 60 Hz frequency). 

All settings are loaded when the module is reset. The stored energy values are saved in FeRAM memory, so they 

are not lost in case of power failure.

It should be noted that the Vrms, Irms, Active Power and frequency values are obtained by direct measurement, 

while the Energy, Reactive Power and cosf values are calculated. 

The measured active power can only be greater than or equal to zero. An example: if the reactive power is -2500 

VAR or +2500 VAR (physical value, electrical network), the corresponding numerical value is +10000 and the 

analogue output (available at the terminals) is +10 V (if SW2-2,3 = "00"). If the reactive power is 0 VAR (physical 

value), the corresponding numeric value is 0 and the analogue output (available at the terminals) is 0 V (if SW2-

2,3 = "00"). Cosfi has the same behaviour as reactive power. For measurement and retransmission ranges in the 

case of 50% and 25% scaling, refer to the tables in the USER MANUAL.

Summary of Contents for Z203-2

Page 1: ...single phase network analyzer SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and configuration software visit www seneca i...

Page 2: ...seneca it products z203 2 Important Obstructing ventilation slots with any object is prohibited Installing the module next to devices that generate heat is prohibited Electrical and electronic waste...

Page 3: ...factor 3 Maximum current 15 A Frequency from 35 to 75 Hz Class Base Prec Voltmeter 0 5 Ammeter 0 5 Wattmeter 0 5 active power ANALOGUE OUTPUT Voltage output 0 10 Vdc 0 5 Vdc minimum load resistance 2...

Page 4: ...ional to the full scale value of the measured quantity For example if the retransmitted signal is in current 4 20 mA and the quantity to retransmit the voltage Vrms we will have that 4 mA will corresp...

Page 5: ...BAUD RATE 19200 38400 57600 1 ADDRESS 2 63 From EEPROM 5 8 DIP Switch status SW2 POSITION DESCRIPTION 1 2 3 4 5 6 7 8 Network frequency 50 Hz NETWORK NOMINAL FREQUENCY SELECTION 50 60 Hz Network frequ...

Page 6: ...nnectors are polarized 2 To secure the module to the DIN rail tighten the two hooks on the side of the IDC10 rear connector USB PORT The module is designed to arrange data according to the modes defin...

Page 7: ...Connection cable signal protection shield recom mended Retransmitted input output The module accepts an input voltage up to 500 Vac maximum Provide the input voltage to terminals 10 and 12 and connect...

Page 8: ...tings procedures refer to the USER MANUAL downloadable from www seneca it products z203 2 ATTENTION The upper power supply limits must not be exceeded as this might cause serious damage to the module...

Reviews: