3.6 ENVIRONMENTAL CONDITIONS

Humidity 

30 – 90 % a 40°C not condensing

Pollution degree

2 (Maximum environment pollution during operations)

Storage Temperature

-20°C – +85°C

The module was designed to be installed on omega IEC EN 60715 rail in vertical position.
We suggest the module installation in the lower part of the control panel.

In order to ensure best performance and longest working life module, please ensure adequated ventilation to 
the modules and avoid placing raceways or other objects which obstructs the ventilation slots.
It’s forbidden ti install the module near or above heat sources.

«

Severe operating conditions

» are as follows:

- High power supply voltage: >30 V

 , 26 V

.

- The module supplies power to the sensor at input.
- Output used as current generator (connected to a passive module).
If the modules are installed side by side,

separate them by at least 5 mm

 in the following cases:

 

-If the panel operating temperature exceeds 45°C and at least one of the severe operating conditions exists;
-If the panel operating temperature exceeds 35°C and at least two of the severe operating conditions exist.

4. PRELIMINARY INSTRUCTIONS FOR USE

To satisfy the electromagnetic compliance requirements:

  Use shielded cables for signals transmission;

 The cable shield must be connected to an earth wire used specifically for instrumentation;

 Avoid placing signal cables near power cables and power appliances (inverters, motors, 
induction ovens etc...).

5. ELECTRICAL CONNECTIONS

5.1 SAFETY MEASURES BEFORE USE

The module has a microUSB connector, you can configure it through APP and/or software.
For more information please see 

.

www.seneca.it/products/z109ui2

Y

x

Z109UI2

USB

PWR

CU-A-MICRO-OTG

CU-A-MICROB

CU-A-MICROB

5.2 USB INTERFACE

5.3 CONNECTIONS

Please provide the module with supply voltage < 40 V

 or < 28 V

.

These upper limits must not be exceeded to avoid serious damage to the module.

5.4 POWER SUPPLY

2

3

19 – 28 V

10 – 40 V

2.5 W Max 

Summary of Contents for Z109UI2

Page 1: ...9 8706287 Internet site Technical assistance www seneca it support seneca it Commercial reference sales seneca it Chapter index Page 1 Preliminary warnings 2 2 Description and characteristics 2 1 Modu...

Page 2: ...d Measurement and re transmission on isolated analog output with voltage and current output DIP switch for selecting type of input START END output mode zero elevation scale inversion output type mA o...

Page 3: ...ards EN61000 6 4 electromagnetic emission in industrial environment EN61000 6 2 electromagnetic immunity in industrial environment EN61010 1 safety Notes Use with copper conductor Use in Pollution Deg...

Page 4: ...y at least 5 mm in the following cases If the panel operating temperature exceeds 45 C and at least one of the severe operating conditions exists If the panel operating temperature exceeds 35 C and at...

Page 5: ...tput 1 6 V Voltage mA output 1 6 A Generated current 3 mA output External power Supply current 4 1 6 A 5 6 ANALOG OUTPUT Electrical ratings for UL Output 10 V 20 mA Input 20 V 20 mA Operating Temp 20...

Page 6: ...e START and END scale desired SW1 INPUT SELECTION POSITIO N INPUT POSITION INPUT 1 2 3 4 TYPE 1 2 3 4 TYPE V mA SW2 START and END POSITIO N START POSITIO N END 1 2 3 SCALE n 4 5 6 SCALE n 1 1 2 2 3 3...

Page 7: ...the type of input START and END measurement which include the required beginning and end values 2 Power up the module 3 Supply a calibrator or simulator of the signal you wish to measure and re transm...

Page 8: ...d information about the recycling of the product please contact your local city office waste disposal service of the retail store where you purchased this product 9 DECOMMISSIONING AND DISPOSAL 8 MODU...

Reviews: