MENU PARAMETERS

PARAMETERS TO SET FROM THE MENU:

 

C..n.F

Parameter code

Parameter name

SETTING RANGE AND DESCRIPTION

DEFAULT VALUE

FUNC

Type of instrument 

operation

0 = frequency and totalizer display function.

1 = only frequency measurement display function.

2 = only totalizer display function.

0 = Instant. and 

Totaliz.

RE

Enables panel totalizer 

reset and auxiliary 

digital input

0 = totalizer reset from panel and auxiliary digital input enabled.

1 = totalizer reset from panel and auxiliary digital input disabled.

0 = Enables

PA

Password enabling for 

menu access

By setting a value other than 

5477

, the password will be requested when 

starting the menu (always 5477).

5477 = Password 

disabled

PARAMETERS TO SET FROM THE MENU:

 

.n.P.t.

type

Input type

1= Reed 

6= Photoelectric (ASTRA)

2= npn 2 wires 

7= HALL

3= npn 24 V (3 wires) 

8= 24 V input

4= pnp 24 V (3 wires) 

9= TTL input

5= NAMUR 

10= Variable reluctance

3 = npn 24 V (3 

wires)

H-f

Full scale (Hz)

Full scale in Hz to measure frequency. It also defines the frequency value 

associated with the 

H-D

 parameter.

Settable values

The decimal point is imposed by 

DPN

.

Minimum value: 0,

Max value depending on the display:

4 / 11 (4+7) digits: 9999 (without decimal point). 6 / 8 digits: 10000 (without 

decimal point).

1000 Hz

dpn

Position of decimal 

point in 

H-F

0 = no decimal point (e.g. 00009999),

1 = first digit (e.g. 0000999.9)

2 = second decimal point (e.g. 000099.99)

3 = third decimal point (e.g. 00009.999),

4 = fourth decimal digit (e.g. 0000.9999, only for 6 and 8 digit models).

0 = Decimal point 

absent

PARAMETERS TO SET FROM THE MENU:

 

s.C.a.L

L-d

Start of the scales 

displaying frequency 

measurement

Frequency value displayed if the measured frequency is 0. Values within 

the limits see: TABLE1.

0

H-d

Full scales 

displaying frequency 

measurement

Displayed frequency value if the measured frequency is 

H-f

.

Value within the limits see: TABLE1.

1000

dp_D

Frequency display 

decimal point position

0 = no decimal point (ex. 12345678),

1 = first digit (e.g. 1234567.8)   ...      ...

N digits display-1

For 11-dig

it models (4+7): max number of decimal places equal to 3

0 = Decimal point 

absent

FLt

Filter level

0= no filter 

1 - 20 

3

Au

Number of samples on 

which to average the 

frequency value

Selectable values: 1 -10.

1

FREQUENCY MEASUREMENT LIMITS:

TOTALIZER LIMITS

DISPLAY DIGITS

MIN. LIMIT

MAX. LIMIT

MIN. LIMIT

MAX. LIMIT

4

-1999

9999

0

9999

6

-199999

999999

0

999999

8

-19999999

99999999

0

99999999

11 (4+7)

-1999

9999999

0

9999999

Summary of Contents for S311D L Series

Page 1: ...git display advanced digital totalizers indicators SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and the configuration sof...

Page 2: ...are not followed 96 mm 98 mm 48 mm WARNING The full content of this manual must be read before any operation The module must only be used by qualified electricians Specific documentation is available...

Page 3: ...pacity 8 A 250 Vac available only on optional board AUX DIGITAL INPUT Optoinsulated Vmin 10 V Vmax 30 V available only on optional board OPERATION DESCRIPTION The measurement of the digital input freq...

Page 4: ...nit at each rising edge of the digital input Decreasing it is decreased by one unit at each rising edge of the digital input Once the maximum or minimum limit is reached counting restarts from zero It...

Page 5: ...l power supply for the sensors equal to 17 Vdc is available at terminals 7 and 10 03 04 05 06 VOLTAGE V 03 04 05 06 APPLIED CURRENT A Active output already powered to be connected to passive inputs 03...

Page 6: ...imum value 0 Max value depending on the display 4 11 4 7 digits 9999 without decimal point 6 8 digits 10000 without decimal point 1000 Hz dpIn Position of decimal point in HI F 0 no decimal point e g...

Page 7: ...on the minimum held threshold does not automatically reset 4 Alarm on the maximum held threshold does not automatically reset 5 Alarm on the totalizer threshold value does not automatically reset 0 N...

Page 8: ...N digits display 1 For 11 digit models 4 7 max number of decimal places equal to 6 0 No decimal point e H I t Confirming with OK MENU you save all parameters on a flash card and after a few moments re...

Reviews: