6/8
MENU PARAMETERS
PARAMETERS TO SET FROM THE MENU:
C..n.F
Parameter code
Parameter name
SETTING RANGE AND DESCRIPTION
DEFAULT VALUE
FUNC
Type of instrument
operation
0 = frequency and totalizer display function.
1 = only frequency measurement display function.
2 = only totalizer display function.
0 = Instant. and
Totaliz.
RE
Enables panel totalizer
reset and auxiliary
digital input
0 = totalizer reset from panel and auxiliary digital input enabled.
1 = totalizer reset from panel and auxiliary digital input disabled.
0 = Enables
PA
Password enabling for
menu access
By setting a value other than
5477
, the password will be requested when
starting the menu (always 5477).
5477 = Password
disabled
PARAMETERS TO SET FROM THE MENU:
.n.P.t.
type
Input type
1= Reed
6= Photoelectric (ASTRA)
2= npn 2 wires
7= HALL
3= npn 24 V (3 wires)
8= 24 V input
4= pnp 24 V (3 wires)
9= TTL input
5= NAMUR
10= Variable reluctance
3 = npn 24 V (3
wires)
H-f
Full scale (Hz)
Full scale in Hz to measure frequency. It also defines the frequency value
associated with the
H-D
parameter.
Settable values
The decimal point is imposed by
DPN
.
Minimum value: 0,
Max value depending on the display:
4 / 11 (4+7) digits: 9999 (without decimal point). 6 / 8 digits: 10000 (without
decimal point).
1000 Hz
dpn
Position of decimal
point in
H-F
0 = no decimal point (e.g. 00009999),
1 = first digit (e.g. 0000999.9)
2 = second decimal point (e.g. 000099.99)
3 = third decimal point (e.g. 00009.999),
4 = fourth decimal digit (e.g. 0000.9999, only for 6 and 8 digit models).
0 = Decimal point
absent
PARAMETERS TO SET FROM THE MENU:
s.C.a.L
L-d
Start of the scales
displaying frequency
measurement
Frequency value displayed if the measured frequency is 0. Values within
the limits see: TABLE1.
0
H-d
Full scales
displaying frequency
measurement
Displayed frequency value if the measured frequency is
H-f
.
Value within the limits see: TABLE1.
1000
dp_D
Frequency display
decimal point position
0 = no decimal point (ex. 12345678),
1 = first digit (e.g. 1234567.8) ... ...
N digits display-1
For 11-dig
it models (4+7): max number of decimal places equal to 3
0 = Decimal point
absent
FLt
Filter level
0= no filter
1 - 20
3
Au
Number of samples on
which to average the
frequency value
Selectable values: 1 -10.
1
FREQUENCY MEASUREMENT LIMITS:
TOTALIZER LIMITS
DISPLAY DIGITS
MIN. LIMIT
MAX. LIMIT
MIN. LIMIT
MAX. LIMIT
4
-1999
9999
0
9999
6
-199999
999999
0
999999
8
-19999999
99999999
0
99999999
11 (4+7)
-1999
9999999
0
9999999