Alarms on frequency or totalizer measurement (optional board):

Two alarms can be activated on the measurement of the frequency of the digital input signal or on the totalizer threshold 

values, each of which, if enabled, can be configured as follows:

1.  Alarm on the minimum threshold.

2.  Alarm on the maximum threshold.

3.  Alarm on the minimum held threshold (does not automatically reset).

4.  Alarm on the maximum held threshold (does not automatically reset).

5.  Alarm on the totalizer threshold value (does not reset automatically).

For each alarm it is possible to set threshold and hysteresis. For the totalizer alarm, the hysteresis is not considered. If the 

alarm is maximum the reset value is Threshold-Hysteresis, if it is minimum the reset value is Thr Hysteresis. The 

status of the alarms can be viewed via the two LEDs on the front panel and from the relays (if the optional board is used). 

The relays switch status when the alarm occurs and return to the initial state when it is reset (if held). The alarms held are 

reset in normal operation by pressing the UP + OK/MENU keys for a few seconds. For the totalizer alarm, the alarms are 

reset by pressing the UP+DOWN+ OK/MENU keys, via MODBUS or from the auxiliary digital input.

Totalizer

As an alternative to measuring the frequency of the digital input signal, it is possible to view the value of the associated 

totalizer (saved in non-volatile memory). Both values are available simultaneously in the 11-digit indicators (4+7).

The totalizer can be:

Increasing: it is increased by one unit at each rising edge of the digital input.

- Decreasing: it is decreased by one unit at each rising edge of the digital input.

Once the maximum or minimum limit is reached, counting restarts from zero.

It is also possible to set a 

reduction ratio

 by which to divide the totalizer value; the resulting value will then be displayed.

Reset

 can also take place in the following three ways: 

- From auxiliary digital input (if enabled). 

- By pressing the three keys simultaneously (if enabled).

- Via Modbus register. 

 

Display of frequency measurement value or totalized value

Three 

types of operation

 can be set (except for the 11-digit models that display both the frequency value and the totalizer 

value together) that define the display modes:

1.  Type 0: both frequency value and totalizer value display. Pressing UP for a few seconds you access the frequency 

display, pressing DOWN for a few seconds displays the totalized value. When passing to the frequency value for a few 

seconds the writing 



 appears, passing to the totalized value the writing 



 appears for a few seconds.

2.  Type 1: frequency measurement display only.

3. 

Type 2: totalizer display only

Average and frequency measurement filtering

The frequency value can be averaged over a settable number of samples. The average value is then filtered through the 

20-level exponential filter and then shown on the display.

VLF Mode

If the full scale in Hz for measuring the frequency (HI-F) ≤ 1 Hz the instrument goes to Very Low Frequency Mode (VLF) 

thanks to which the minimum detectable frequency value is equal to 0.00015 Hz (1 pulse every 111 minutes).

Password to access the menu

It is possible to enable password protection from the Programming Menu. The Quick Alarm Menu is always free of 

passwords.

Summary of Contents for S311D L Series

Page 1: ...git display advanced digital totalizers indicators SENECA s r l Via Austria 26 35127 PADOVA ITALY Tel 39 049 8705355 8705359 Fax 39 049 8706287 For manuals in other languages and the configuration sof...

Page 2: ...are not followed 96 mm 98 mm 48 mm WARNING The full content of this manual must be read before any operation The module must only be used by qualified electricians Specific documentation is available...

Page 3: ...pacity 8 A 250 Vac available only on optional board AUX DIGITAL INPUT Optoinsulated Vmin 10 V Vmax 30 V available only on optional board OPERATION DESCRIPTION The measurement of the digital input freq...

Page 4: ...nit at each rising edge of the digital input Decreasing it is decreased by one unit at each rising edge of the digital input Once the maximum or minimum limit is reached counting restarts from zero It...

Page 5: ...l power supply for the sensors equal to 17 Vdc is available at terminals 7 and 10 03 04 05 06 VOLTAGE V 03 04 05 06 APPLIED CURRENT A Active output already powered to be connected to passive inputs 03...

Page 6: ...imum value 0 Max value depending on the display 4 11 4 7 digits 9999 without decimal point 6 8 digits 10000 without decimal point 1000 Hz dpIn Position of decimal point in HI F 0 no decimal point e g...

Page 7: ...on the minimum held threshold does not automatically reset 4 Alarm on the maximum held threshold does not automatically reset 5 Alarm on the totalizer threshold value does not automatically reset 0 N...

Page 8: ...N digits display 1 For 11 digit models 4 7 max number of decimal places equal to 6 0 No decimal point e H I t Confirming with OK MENU you save all parameters on a flash card and after a few moments re...

Reviews: