c. Enable and set the phase overcurrent, neutral overcurrent, residual overcurrent and negative-sequence 

overcurrent elements (up to four elements of each type) as required by the application.

d. Enable and set the phase time-overcurrent (TOC), maximum phase TOC, negative-sequence TOC, 

neutral-ground TOC, and the residual-ground TOC elements as required by the application.

e. Enable and enter RTD settings if RTDs are supported by the relay and used for the application.

f. If ac voltage inputs are supported by the relay, enable and set the undervoltage and overvoltage elements as 

required by the application.

g. If synchronism check elements are supported in the relay, enable and enter the settings per the guidance 

provided in Section 4 of the SEL-751A manual.

h. Enable and set the frequency and rate-of-change of frequency elements (if supported and used for the 

application).

i.

Enable and set the power factor elements (if supported and used for the application).

j.

Set the trip/close logic settings using the Relay Word bits of the enabled protection and logic elements to drive 
the breaker trip logic.

k. Enable and set the recloser control elements if the relay supports the recloser control option.

l.

Enable and set demand and peak demand metering.

Group 1 Logic Settings

Enable and enter SEL

OGIC

 equations settings as needed by the application.

Repeat above steps for Group 2 and 3 settings if required by the application.

Global Settings

Review, enable, and enter the Global settings required by the application. Global settings include event messenger, 
synchrophasors, breaker failure, arc-flash protection, etc.

Front-Panel Settings

a. Configure relay display points. Use the front-panel display to indicate fault conditions, alarms, and operational 

parameters.

b. Configure relay front-panel target indications.

Report Settings

a. Configure relay event reporting (ER) to capture relay trip conditions.

b. Configure and set the SER (sequence-of-events report) settings.

c. Configure and set the LDP (load profile report settings) report, if required.

Communications Ports and Protocol Settings

Enable and enter the communications ports and protocol settings as required by the application.

Step 4. Save the revised setting file into the database, and then with the settings still open, click the 

Send Active Settings

 

icon 

 and then click 

OK

 when prompted to upload the revised settings into relay.

Step 5. Perform relay verification and commissioning tests per your requirements. Refer to Section 10 in the SEL-751A 

manual for details on relay testing.

*PLS751A-01*

© 2007–2009 Schweitzer Engineering Laboratories, Inc. All rights reserved.

Date Code 20090

109

Relay Settings

Courtesy of NationalSwitchgear.com

Summary of Contents for SEL-751A

Page 1: ...et Serial Port Cover Configurable Label Kit if equipped Label Removal Tool Blank Pushbutton LED Label 198 0424 RIGHT UP Blank Target LED Label 198 0424 LEFT UP For Additional Technical Assistance Call...

Page 2: ...ONTROL INPUTS INPUT POWER OUTPUT CONTACTS SEL 751A Feeder Protection Relay A diagram for a four wire wye connection is also available in the instruction manual Power Supply 110 230 Vac 24 48 Vdc 110 2...

Page 3: ...g location and trace 2 Make smooth cut around cutout 3 Place mounting gasket around relay and insert unit into hole The photo displays optional appearance bezel 4 Fasten relay to mounting plate with i...

Page 4: ...p 3 Connect up to 2 digital inputs per application requirements to optoisolated inputs IN101 terminals 10 and 11 and IN102 terminals 11 and 12 Step 4 Connect the 3 output contacts per application requ...

Page 5: ...agram For other PT connection options refer to Section 2 of the SEL 751A manual Card Slot Z Current Inputs Card Connect phase current and neutral current inputs as shown in the typical connections dia...

Page 6: ...your choice for the connection Then you will choose which port to connect through Make sure you select the same port that you connected the cable to then click OK Step 4 Set the PC terminal emulation...

Page 7: ...LERATOR QuickSet SEL 5030 Software a Connect the relay to a PC using an SEL C234A serial or SEL C662 USB cable b Apply power to the relay c Start the ACSELERATOR QuickSet software program and establis...

Page 8: ...tering Group 1 Logic Settings Enable and enter SELOGIC equations settings as needed by the application Repeat above steps for Group 2 and 3 settings if required by the application Global Settings Revi...

Reviews: