SEG Electronics GmbH
DOK-HB-CSPFHPTE
4
Retrofit Kit for the Replacement of System Line CSP2-F by HighPROTEC MCA4
General Information
Retrofit-kit for the replacement of a System Line device by a HighPROTEC device.
→
As the CSP System Line series of protection and control devices has been phased out, it is now
necessary to replace them with new protection and control devices if necessary.
→
SEG Electronics GmbH provides a retrofit-kit with which the devices of the System-Line can be
exchanged for devices of the HighPROTEC with minimum effort. The existing control cabinet door
can still be used. No need to saw a new door cutout. There is no need to drill a hole for fixing.
→
Where it is not possible to take over certain functions by simply setting the parameters, appropriate
logic blocks can be used and parameterised in the HighPROTEC series.
→
The HighPROTEC devices offer more communication options, protection and monitoring functions
at a significantly lower price.
→
In addition, these devices offer more possibilities for error analysis (disturbance recorders).
NOTICE
The CSP2 has several control outputs with separate power circuit for direct
control of switching devices. These are no longer available with HighPROTEC
devices. Therefore, check whether the output relays of the HighPROTEC are
designed for this current load (see "DOK-HB-MCA4-2E" manual >> Technical
Data) or whether additional coupling relays may have to be used.
Procedure Before Starting the Remodeling on Site:
→
The mechanical possibilities (space; sufficient installation depth) must also be checked before
remodeling!
→
Define communication protocol.
→
Determine the distance of the entire cable section.
→
Wiring diagrams must be adapted.
→
The parameterization must be created for the new protective device.
→
The secondary inspection must be planned after the remodeling has been completed.