SEG Electronics GmbH
DOK-HB-CSPFHPTE
13
Retrofit Kit for the Replacement of System Line CSP2-F by HighPROTEC MCA4
4. Assembly of the HighPROTEC Device
•
Push the HighPROTEC device into the cover frame.
•
Then screw the device to the control cabinet door using the
supplied screw-nuts.
Wiring of the HighPROTEC device (1)
•
Check whether the cross-section of the cable duct is
sufficient. As a rule, a larger cable duct is recommended.
•
Start the rewiring on the door side (device side). The cables
of each module should be connected to a string by cable ties.
The strings must be clearly marked.
•
Install an additional empty conduit so that the complete wire
harness can be safely routed into the medium voltage cell.
•
Feed the cable harnesses through the empty conduits into the MS cell.
Wiring of the HighPROTEC device (2)
•
Connect the wires to the corresponding terminal strips (according to the circuit diagram).
•
To avoid possible wiring errors, check the correct cable occupation with a continuity tester.