SEG Electronics GmbH
DOK-HB-CSPFHPTE
14
Retrofit Kit for the Replacement of System Line CSP2-F by HighPROTEC MCA4
5. Commissioning and Protection Test of the System Must be Carried out by
a Commissioning Engineer
NOTICEHINWEIS
SEG Electronics GmbH can take over the commissioning and protection testing for
your system.
Please contact the
SEG Electronics GmbH
service team if required.
All functions of the CSP2-F can be easily covered by the HighPROTEC MCA4.
→
Where it is not possible to take over certain functions by simply setting the parameters,
corresponding logic modules can be used and parameterised in the HighPROTEC series.
→
Otherwise it is important to adjust the number of inputs and outputs of the old wiring with the new
devices. For example, the complete System Line devices had a very large number of digital inputs.
→
These can be covered by selecting the appropriate hardware variant of the MCA4. Note that some
information is no longer exchanged via digital inputs, but via communication protocols
(e.g. IEC 61850).
DANGER
Dangerous voltages!
Observe the usual protective measures, legal regulations and local
guidelines.
Especially before any work:
•
Unlock
•
Secure against being switched on again
•
Check that there is no voltage
•
Grounding and short-circuiting
•
Cover or isolate adjacent live parts.
NOTICE
When selecting the appropriate device type for the MCA4, ensure a sufficient
number of digital inputs/outputs.