SEELEY INTERNATIONAL - INSTALLATION MANUAL  

|  

17

 

COMMISSIONING THE COOLER

CORRECT WATER LEVEL

With the water pump still disconnected, turn on the water supply 

and allow the tank to fill. If you have installed the drain valve 

instead of the bleed funnel you will need to turn the water on by 

pressing 

 on the wall control while it is in the OFF state. 

The water inlet valve will now remain open for 15 minutes.

COMMISSIONING THE COOLER 

cont.

TEST OPERATION

Check that the green light on the Electronics Module is on. This 

indicates that power is connected to the Electronics Module. 

Make sure that the flexible cover on the Electronics Module is 

fully closed as shown. 

ILL1095-B

ILL1085-A

ILL997-C

ILL998-D

ILL1061-C

When the tank is full the float valve will stop the water entering 

the air cooler. Wait for this to happen and observe the level. The 

correct water level is approximately 5mm below the surface of 

the tank the float valve is mounted on. If the level is too high 

rotate the float clockwise. If it is too low rotate the float anti-

clockwise, as shown.
If you installed the Drain Valve, a complete drain can be initiated 

by holding down both 

 and 

 for 1 second when the 

wall control is OFF. The signal “dr” will display to confirm the 

drain operation has activated.

WATER PUMP CONNECTION

Switch off the electronics module. Route the pump cord as 

shown and connect the pump to the electronics module. Switch 

the electronics module on.

WARNING! Do not run the pump while the pad frames are 

off and the fan is on.

Replace the pad frames and run the air cooler. To start the 

air cooler, press the power button on the wall control. If it 

has not been on before it will start in Manual control mode 

(“Man” will display as shown). The display will flash “Pre-Cool 

Cycle”as shown and the pump will soon operate to saturate the 

pads. This will take a few minutes and then the fan will start 

automatically.
Ensure the air cooler operates correctly and does not leak 

water. Make sure that the air flow from the outlets is balanced 

and that there are no air leaks in the ducting.
If you installed the drain valve, test that the drain valve opens 

by holding down both 

 and 

 for 1 second when the 

wall control is OFF. The signal “dr” will display to confirm the 

drain operation has activated.

Stop the air cooler and check that each of the pads are evenly 

saturated. 
Finally, instruct the owner on how to operate the new air cooler.

Summary of Contents for Breezair TBA Series

Page 1: ...INSTALLATION MANUAL TBA Evaporative Cooler Original English Instructions English TBA ...

Page 2: ......

Page 3: ... the Retailer to serious liability CABLE LENGTHS STANDARD WALL CONTROL 2 COOLER COMPONENTS 3 SAFETY NOTES 4 SPECIFICATIONS 5 COMPONENTS OF THE AIR COOLER 6 DISMANTLING THE COOLER 7 INSTALLING THE TRANSITION 8 INSTALLING ELECTRIC CABLES 9 WATER CONNECTIONS 10 ELECTRICAL CONNECTION 12 INSTALLING THE FAN ASSEMBLY 13 WALL CONTROL LOCATION 14 INSTALLING THE WALL CONTROL 14 PROGRAMMING THE WALL CONTROL ...

Page 4: ...2 TBA Evaporative Cooler CABLE LENGTHS STANDARD WALL CONTROL ...

Page 5: ...SEELEY INTERNATIONAL INSTALLATION MANUAL 3 COOLER COMPONENTS ILL1457 C ...

Page 6: ...lothing when working with power tools Always ensure that electrical power cables conform to relevant government safety requirements Always lift the cooler to its location using safe methods and equipment Never drain the cooler directly onto the roof Always use pipes to carry the drain water to a proper point Failure to do this can stain the roof and make the roof slippery and unsafe All installati...

Page 7: ... Electronics Module and push the manual reset toggle switch located underneath the Electronics Module The isolation switch on the module cannot be turned on without the securing screw being in place If at any time the electrical supply cable is damaged it must be replaced by a special cord or assembly available from the manufacturer or its service agent in order to avoid a hazard WATER Specificati...

Page 8: ...cts the Float Valve to the Solenoid Valve 9 Water Tank reservoir 10 Corner Pillar 11 Water Sensor detects conductivity of water 12 Float Valve for control of main water supply level in the Water Tank 13 Water Pump 14 Drain Valve for releasing water in the tank automatically or when the user requires 15 Motor Cable with two plugs 16 Electric Power Supply Cable with plug 17 Electronics Module 18 Pum...

Page 9: ... plug With both arms hold each side of the Venturi fan assembly Press the large clips at each side and lift the Venturi fan assembly upwards and carry it out of the cabinet Note Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker provided When restraining cable is fitted TBA450 60Hz models and TBA550 all models Place the Venturi fan assembly ...

Page 10: ...herseal opening fully as that will reduce the air cooler performance Check that the weatherseal flaps do not interfere with the duct or any screws The flaps should move freely through 90º See diagram The top edge of the duct must be level The Weatherseal requires a 270mm section of straight duct under the air cooler before a bend is installed Do not penetrate the duct with any fasteners in this se...

Page 11: ...ake the power cable and drop the non plug end down the hole where the Electronics Module was and pass it through the conduit adaptor factory fitted in the Transition Then lock the plug on the other end in place as shown see diagram Pass the taped end of the wall control cable through the conduit adaptor also and leave about 0 5m 20 in the Water Tank Now pass the cables through your main conduit an...

Page 12: ...pplied Any old hose sets should not be re used Make sure all washers and o rings are fitted correctly Do not over tighten plastic threads ILL985 E Attach the Drain Adaptor under the Drain Valve and attach a pipe to carry the water to a suitable drain point Do not allow water to run freely onto the roof it will stain the roof See diagram The Water Sensor protects the pump and helps control water sa...

Page 13: ...70 C Cooler Models Plugs TBA250 1 Plug in TBA350 1 Plug in TBA450 2 Plugs in TBA550 2 Plugs in WATER CONNECTIONS cont BLEED FUNNEL ALTERNATIVE The bleed funnel is a simplified alternative to the drain valve It also provides overflow and drain features Assemble the bleed funnel to the Water Tank as shown Make sure the o rings are fitted correctly Screw the nut tight by hand Attach the Drain Adaptor...

Page 14: ... a shut off valve do not use a non return type valve close by the air cooler In areas where freezing might occur always install a drain down point for the mains water supply The water connection is 1 2 inch BSP male thread Now the Electronics Module must be re fitted First take the wall control cable and the Solenoid Valve cable if installed that are loose in the Water Tank and route them out from...

Page 15: ...place the pad frames except the front padframe to allow access ILL1076 E ILL1229 D INSTALLING THE FAN ASSEMBLY Carry the Venturi Fan assembly to the air cooler and fit it back in place It will only fit one way Note Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker Lower the Venturi Fan assembly into place ensuring the cables sit in the chan...

Page 16: ...eat sources A position in direct line of a cooling outlet Mounting the wall control in a position near any heat source or cooling outlet will affect its ability to control temperature The Wall Control cable will plug into the back of the Control Note For brick walls position the template so the screw and cable holes are not located into the mortar between the bricks WARNING Ensure there are no ele...

Page 17: ...be started within four 4 minutes of power being applied to the wall control If this time has elapsed then turn off power to the air cooler for a minimum of 6 seconds before starting the following procedure SET UP FOR BLEED FUNNEL If you installed the Bleed Funnel instead of the Drain Valve then you will need to set the wall control and cooler for manual bleed operation 1 While the wall control is ...

Page 18: ... be set to replace some water after a set time of cooling operation with the following procedure 1 While the wall control is OFF hold down AUTO for at least 3 seconds 2 Press while pressing AUTO A1 displays 3 Release Auto Press until A6 displays 4 Press 5 00 will display Press until 01 displays 6 Press 7 A6 will display Press until A8 displays 8 Press 9 A number will be displayed Press or until th...

Page 19: ...e drain can be initiated by holding down both and for 1 second when the wall control is OFF The signal dr will display to confirm the drain operation has activated WATER PUMP CONNECTION Switch off the electronics module Route the pump cord as shown and connect the pump to the electronics module Switch the electronics module on WARNING Do not run the pump while the pad frames are off and the fan is...

Page 20: ... been removed Check for loose fan blades No water drain function drain valve coolers only Drain valve failure Replace drain valve Drain valve incorrectly connected to electronics module Check plug connection and orientation Water sensor not operating Check sensor Clean sensor No water from drain hose Check for blockages in the drain hose Unit will not run Wall control display fault No power to coo...

Page 21: ...SEELEY INTERNATIONAL INSTALLATION MANUAL 19 2 x 5mm 3 16 Plasterboard or 2 x 6mm 1 4 Brick 16mm 5 8 65mm 2 55 31mm 1 22 ILL1135 C ...

Page 22: ...valve Solenoid cable Pump cable Probe cable The owner has been instructed how they can electrically isolate the unit at the meter box in case of an emergency All ducts are hung correctly and there are no air leaks The system has been run from the customers wall control and all functions work correctly All wall holes behind the controller have been sealed The air balance for all outlets have been a...

Page 23: ... local Breezair distributor seeleyinternational com service It is the policy of Seeley International to introduce continuous product improvement Accordingly specifications are subject to change without notice Please consult with your dealer to confirm the specifications of the model selected AU 1504 839479 K ...

Reviews: