TBA Evaporative Cooler

 

INSTALLING THE TRANSITION

INSTALLING THE TRANSITION 

cont.

ILL1049-B

ILL969-B

ILL1179-C

ILL965-B

ILL967-B

The air cooler is designed to be fixed to the first section of the 

duct without any additional frame for support. Therefore make 

sure the duct is fixed to the building using a strong method. 

The duct size must be 550 x 550mm. The top edge must be 

strong without any flange. 

Use a spirit level in both directions to get the Transition level. 

Screw it to the duct using the eight (8) screws provided. There 

are eight (8) V-notch locations for the screws. See diagram.

Now break off both clips on the Transition that retain the 

Weatherseal.

IMPORTANT! 

There must be no obstructions to the 

weatherseal opening fully as that will reduce the air cooler 

performance.

Check that the weatherseal flaps do not interfere with the duct 

or any screws. The flaps should move freely through 90º. See 

diagram.

The top edge of the duct must be level. The Weatherseal 

requires a 270mm section of straight duct under the air cooler 

before a bend is installed. Do not penetrate the duct with any 

fasteners in this section.
The best location for the cooler is where the air is fresh and 

clean. Keep away from exhaust vents from factories and 

commercial kitchens. Do not locate the air cooler near the 

ground where there is dust and pollution.
The sides of the cooler should be a minimum of 600mm from 

any wall.

If the cooler is located on a platform, always build a safety 

rail around the platform.

Place the transition onto the duct. If the roof is sloped then 

make sure the transition is located correctly according to the 

diagram.

Summary of Contents for Breezair TBA Series

Page 1: ...INSTALLATION MANUAL TBA Evaporative Cooler Original English Instructions English TBA ...

Page 2: ......

Page 3: ... the Retailer to serious liability CABLE LENGTHS STANDARD WALL CONTROL 2 COOLER COMPONENTS 3 SAFETY NOTES 4 SPECIFICATIONS 5 COMPONENTS OF THE AIR COOLER 6 DISMANTLING THE COOLER 7 INSTALLING THE TRANSITION 8 INSTALLING ELECTRIC CABLES 9 WATER CONNECTIONS 10 ELECTRICAL CONNECTION 12 INSTALLING THE FAN ASSEMBLY 13 WALL CONTROL LOCATION 14 INSTALLING THE WALL CONTROL 14 PROGRAMMING THE WALL CONTROL ...

Page 4: ...2 TBA Evaporative Cooler CABLE LENGTHS STANDARD WALL CONTROL ...

Page 5: ...SEELEY INTERNATIONAL INSTALLATION MANUAL 3 COOLER COMPONENTS ILL1457 C ...

Page 6: ...lothing when working with power tools Always ensure that electrical power cables conform to relevant government safety requirements Always lift the cooler to its location using safe methods and equipment Never drain the cooler directly onto the roof Always use pipes to carry the drain water to a proper point Failure to do this can stain the roof and make the roof slippery and unsafe All installati...

Page 7: ... Electronics Module and push the manual reset toggle switch located underneath the Electronics Module The isolation switch on the module cannot be turned on without the securing screw being in place If at any time the electrical supply cable is damaged it must be replaced by a special cord or assembly available from the manufacturer or its service agent in order to avoid a hazard WATER Specificati...

Page 8: ...cts the Float Valve to the Solenoid Valve 9 Water Tank reservoir 10 Corner Pillar 11 Water Sensor detects conductivity of water 12 Float Valve for control of main water supply level in the Water Tank 13 Water Pump 14 Drain Valve for releasing water in the tank automatically or when the user requires 15 Motor Cable with two plugs 16 Electric Power Supply Cable with plug 17 Electronics Module 18 Pum...

Page 9: ... plug With both arms hold each side of the Venturi fan assembly Press the large clips at each side and lift the Venturi fan assembly upwards and carry it out of the cabinet Note Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker provided When restraining cable is fitted TBA450 60Hz models and TBA550 all models Place the Venturi fan assembly ...

Page 10: ...herseal opening fully as that will reduce the air cooler performance Check that the weatherseal flaps do not interfere with the duct or any screws The flaps should move freely through 90º See diagram The top edge of the duct must be level The Weatherseal requires a 270mm section of straight duct under the air cooler before a bend is installed Do not penetrate the duct with any fasteners in this se...

Page 11: ...ake the power cable and drop the non plug end down the hole where the Electronics Module was and pass it through the conduit adaptor factory fitted in the Transition Then lock the plug on the other end in place as shown see diagram Pass the taped end of the wall control cable through the conduit adaptor also and leave about 0 5m 20 in the Water Tank Now pass the cables through your main conduit an...

Page 12: ...pplied Any old hose sets should not be re used Make sure all washers and o rings are fitted correctly Do not over tighten plastic threads ILL985 E Attach the Drain Adaptor under the Drain Valve and attach a pipe to carry the water to a suitable drain point Do not allow water to run freely onto the roof it will stain the roof See diagram The Water Sensor protects the pump and helps control water sa...

Page 13: ...70 C Cooler Models Plugs TBA250 1 Plug in TBA350 1 Plug in TBA450 2 Plugs in TBA550 2 Plugs in WATER CONNECTIONS cont BLEED FUNNEL ALTERNATIVE The bleed funnel is a simplified alternative to the drain valve It also provides overflow and drain features Assemble the bleed funnel to the Water Tank as shown Make sure the o rings are fitted correctly Screw the nut tight by hand Attach the Drain Adaptor...

Page 14: ... a shut off valve do not use a non return type valve close by the air cooler In areas where freezing might occur always install a drain down point for the mains water supply The water connection is 1 2 inch BSP male thread Now the Electronics Module must be re fitted First take the wall control cable and the Solenoid Valve cable if installed that are loose in the Water Tank and route them out from...

Page 15: ...place the pad frames except the front padframe to allow access ILL1076 E ILL1229 D INSTALLING THE FAN ASSEMBLY Carry the Venturi Fan assembly to the air cooler and fit it back in place It will only fit one way Note Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker Lower the Venturi Fan assembly into place ensuring the cables sit in the chan...

Page 16: ...eat sources A position in direct line of a cooling outlet Mounting the wall control in a position near any heat source or cooling outlet will affect its ability to control temperature The Wall Control cable will plug into the back of the Control Note For brick walls position the template so the screw and cable holes are not located into the mortar between the bricks WARNING Ensure there are no ele...

Page 17: ...be started within four 4 minutes of power being applied to the wall control If this time has elapsed then turn off power to the air cooler for a minimum of 6 seconds before starting the following procedure SET UP FOR BLEED FUNNEL If you installed the Bleed Funnel instead of the Drain Valve then you will need to set the wall control and cooler for manual bleed operation 1 While the wall control is ...

Page 18: ... be set to replace some water after a set time of cooling operation with the following procedure 1 While the wall control is OFF hold down AUTO for at least 3 seconds 2 Press while pressing AUTO A1 displays 3 Release Auto Press until A6 displays 4 Press 5 00 will display Press until 01 displays 6 Press 7 A6 will display Press until A8 displays 8 Press 9 A number will be displayed Press or until th...

Page 19: ...e drain can be initiated by holding down both and for 1 second when the wall control is OFF The signal dr will display to confirm the drain operation has activated WATER PUMP CONNECTION Switch off the electronics module Route the pump cord as shown and connect the pump to the electronics module Switch the electronics module on WARNING Do not run the pump while the pad frames are off and the fan is...

Page 20: ... been removed Check for loose fan blades No water drain function drain valve coolers only Drain valve failure Replace drain valve Drain valve incorrectly connected to electronics module Check plug connection and orientation Water sensor not operating Check sensor Clean sensor No water from drain hose Check for blockages in the drain hose Unit will not run Wall control display fault No power to coo...

Page 21: ...SEELEY INTERNATIONAL INSTALLATION MANUAL 19 2 x 5mm 3 16 Plasterboard or 2 x 6mm 1 4 Brick 16mm 5 8 65mm 2 55 31mm 1 22 ILL1135 C ...

Page 22: ...valve Solenoid cable Pump cable Probe cable The owner has been instructed how they can electrically isolate the unit at the meter box in case of an emergency All ducts are hung correctly and there are no air leaks The system has been run from the customers wall control and all functions work correctly All wall holes behind the controller have been sealed The air balance for all outlets have been a...

Page 23: ... local Breezair distributor seeleyinternational com service It is the policy of Seeley International to introduce continuous product improvement Accordingly specifications are subject to change without notice Please consult with your dealer to confirm the specifications of the model selected AU 1504 839479 K ...

Reviews: