DU/SD SERIES INSTALL OPERATION MAINTENANCE MANUAL
|
15
INSTALLATION INFORMATION
Table 7: Unit with Blower Corner Weights
Figure 3: Unit with Blower Corner Weights
D
C
A
B
AMI076-A
MODEL
A
B
C
D
DU12
67kg
83kg
75kg
45kg
DU16
82kg
76kg
56kg
63kg
SD26
133kg
90kg
68kg
89kg
SD30
124kg
112kg
74kg
81kg
SD35
131kg
141kg
122kg
88kg
SD40
133kg
159kg
143kg
77kg
AMI118-A
MODEL
A
B
C
D
DU12
47kg
37kg
33kg
37kg
DU16
48kg
42kg
35kg
39kg
SD26
71kg
52kg
43kg
58kg
SD30
51kg
76kg
74kg
43kg
SD35
54kg
95kg
95kg
44kg
SD40
98kg
69kg
63kg
87kg
Figure 4: Single Unit Corner Weights
Table 6: Single Unit Corner Weights
3.2.3 Plant Room
Do not locate unit in an enclosed plant room unless sufficient openings are available to ensure air pressure in the plant
room
CANNOT
become negative with all items in the plant room operating. Mechanical ventilation may be required.
Failure to achieve positive plant room pressure will result in gas combustion gasses being drawn into the room being
heated, presenting a health risk to any occupant. A suitably qualified engineer must be consulted when considering this
type of installation.
3.2.4 Weight and Location
For roof mounting, the building’s roof must be adequately designed to support the unit weight and any service
personnel. If in doubt a suitably qualified Civil or Structural Engineer should be engaged to conduct an assessment.
The below figures and tables list the corner weights of the units with and without blower.