![SEELEY INTERNATIONAL AIRA DU SD Series Installation And Operation Manual Download Page 16](http://html.mh-extra.com/html/seeley-international/aira-du-sd-series/aira-du-sd-series_installation-and-operation-manual_1233142016.webp)
14
|
AMI043-A
Figure 2: Service Clearance around Unit
INSTALLATION INFORMATION
3.2 INSTALLATION
The following recommendations are not intended to supplant or take precedence over relevant official regulations. AIRA
DU / SD units are designed essentially as a roof top or external ground mount unit.
3.2.1 Location
This equipment is not designed for long and complex air distribution ductwork and as such the unit should be located
as close as practicable to the points of air distribution. Depending on large volumes of 100% fresh air, care must
be taken to locate the unit clear of kitchen exhausts, heavy vehicle traffic, industrial fume discharge etc. that may
allow odour or fume laden air to be drawn into the unit. The prime requisites for the correct location of a unit is an
unrestricted supply of clean fresh air. Units shall not be installed in an environment where negative pressure is exerted
on the unit. If the unit is installed indoors a qualified engineer shall be engaged to ensure that the unit is not subject to
negative pressure.
Failure to do so may result in fatalities.
When selecting a location for the DU / SD unit the following shall be considered.
1.
Will the unit be suitably protected from the effects of corrosion and/ or dust laden environments and any likelihood
of physical damage?
2.
Can qualified personnel perform functional adjustments and maintenance on the unit?
3. Does the chosen location prevent a hazard to the building or structure or to the contents of the building?
4.
How to minimise the risks associated with storage, use or release of hazardous or flammable substances in the
vicinity of the unit?
5. How to minimise risk of harm to persons?
6.
Will the noise of the unit operating affect persons nearby? Units should be located so that quiet areas such as
bedrooms, living rooms, meetings rooms etc. are not affected for both the premises that the unit is being installed
and adjoining properties.
7. A structural engineer is to be engaged to prove that the supporting structure is suitable for a fully laden unit.
8. Ensure any skylights within 3m of the units have adequate fall protection installed.
3.2.2 Clearance Around Unit
1200mm is the recommended clearance around all sides for service access. All combustibles must be kept outside the
1200mm clearance zone
1200MM
SERVICE
ACCESS
BOTH SIDES
1200MM
UNDER
DUCTWORK
1200MM
INTAKE