Interfaces & connections
Mounting and Installation, Technical Description, T 811 065 en
19 / 41
3.3
Connection of monitored inputs and outputs
The X10 connector plug on the B7-CPB11 main control unit is for connecting the transmission unit (main detector) and alarm
unit (sirens) for loads between 16
Ω
and 1 k
Ω
. The interface includes two 1.5 A control outputs monitored for short-circuit and
wire breakage and 2 monitored inputs. The OM1 output has a feedback input for external trigger confirmation.
X10 connector plug
Pin
Designation
Function
1
OM1+
+24V
2
OM1-
GND
3
OM1CF+/-
Feedback input
4
OM2+
+24V
5
OM2-
GND
6
IM1+
Input 1
7
IM1-
GND
8
IM2+-
Input 2
9
IM2-
GND
3.3.1
Technical data
Monitored outputs OM1 and OM2
Output voltage:
22 V min., 24 V typical, 28 V max.
Output current:
max. 0.5 A (TUS max. 0.1 A)
OM modes of operation:
Monitored output with area 1 and 2 or TUS (TUS only for OM1),
Planning with software; see table for values
Feedback input:
Feedback from MDLF
Input current
3.1 mA
Polarity
Feedback contact can switch to plus and minus
Output
voltage
Mode of
operation
Load range
Output current
Quiescent
current
Short-circuit current
Line resistance
22V to 28V
Range 1
160-1000
Ω
max. 0.5 A
1 mA
Typically 1.75 A
max. 50
Ω
Range 2
57-375
Ω
max. 0.5 A
3 mA
Typically 1.75 A
max. 20
Ω
TUS
(only OM1)
max. 0.1 A
Typically 0.137 A
max. 20
Ω
Range 1
160-1000
Ω
max. 0.5 A
1 mA
Typically 1.75 A
max. 50
Ω
Range 2
57-375
Ω
max. 0.5 A
3 mA
Typically 1.75 A
max. 20
Ω
Monitored inputs IM1 and IM2
Purpose:
Polling galvanically isolated contacts or key safes and isolating facilities
Monitoring voltage:
Typically 24 V
Monitoring current:
Typically 3.1 mA
Short-circuit current:
Typically 3.63 mA
Termination resistance:
220
Ω
Initiating resistance:
220
Ω
Line resistance:
50
Ω
max.