Housing design & mounting
12 / 41
Mounting and Installation, Technical Description, T 811 065 en
2
Housing design & mounting
The B7-CPB11 main control unit of the SecuriFire 500 contains interfaces for connecting an addressable loop, 2 monitored
inputs and outputs for each alarm transmission and transmission unit compliant with EN 54, and 3 relay outputs. The power
supply unit is integrated on the main control unit.
Every SecuriFire 500 control panel consists of:
•
Housing for wall mounting with door (with control panel, without
printer)
•
B7-CPB11 main control unit with
1x SecuriLine eXtended loop (max. 250 participants, max. 3,500 m)
2 primary outputs
2 primary inputs
3 relay outputs
EPI bus connection (max. 3 devices, max. 1 m)
•
24 V / 2.5 A power supply unit (integrated)
•
2 pcs. 12 V / 7.2 Ah emergency power batter-
ies in series
•
Mains terminals and battery cable
•
Integrated indication and control map (B7-
MIC11)
2
3
4
5
6
1a
1b
11
Fig. 2 Inside view of housing
1a
Plastic housing / door
1b
Plastic housing / rear wall
2
Mounting main indication and control map
3
Main indication control map connection
4
Main control unit
5
Integrated power supply unit
6
Batteries
7
Holes for wall mounting
8
Mains connection entry
9
Loop line and input/output entry
10
EPI bus and Ethernet entry
11
The cable can also be conveyed through the bottom side
of the housings on surface mounting. To do so, it is neces-
sary to drill out the prepared location with a so-called ta-
pered bit. The cable can then be conveyed through the
centre part between the batteries to the connection on the
main control unit.
7
7
7
7
8
9
10
Fig. 3 Rear view of housing