Interfaces & connections
Mounting and Installation, Technical Description, T 811 065 en
15 / 41
3.2
Power supply
For the power supply from the mains network, a circuit of 230V / 50 Hz (110 V / 60 Hz) must be planned; it must have auto-
matic cut-outs (min. 10 A surge resistant) and have its own FI safety switch (U characteristic).
Notice
Installation of the SecuriFire 500 system components and the mains connection may be performed only by tech-
nicians trained specifically for this purpose; installation must always adhere to the applicable rules and regula-
tions of the country concerned (e.g. DIN, VDE).
The fire alarm system must be operated via its own line network. All work is to be carried out in a de-energized
state (mains and battery) and without external voltage.
When manipulating the individual units, it is imperative that you observe the regulations regarding precautions
against static charges (ESD protective measures).
3.2.1
Mains connection
From building distributor
Fuse at least 10A
Own Fl switch
Bayonet fuses
L1
N
PE
BATTERY
12V - 7Ah
8A
BATTERY
12V - 7Ah
Bat
- +
N L PE
B7-CPB11
8A
Fig. 7 Mains connection
X1 connector plug
Designation
Pin
L
1
N
2
PE
3
The mains cable is introduced into the control panel through the opening in the rear wall and is connected to the B7-CPB11
main control unit on the terminal for this purpose. The PE protective earth is connected to the marked earth screw; the battery
cable set is packaged with each control panel and is connected to the power supply unit and batteries.
3.2.2
Technical data
Connection:
~230 V / 110 V (± 15%)
Mechanical design:
3-pin screw terminal, RM 3.81
cable cross-section of 0.14 to 2.5 mm
2