Commissioning
Mounting and Installation, Technical Description, T 811 065 en
37 / 41
6 Commissioning
Notice
Planning, mounting, commissioning and maintaining fire detection systems require special knowledge and may
be carried out only by trained specialists. The product-specific training of qualified personnel is to be provided by
Securiton or by persons expressly authorised to do so by Securiton.
6.1
Program
The SecuriFire 500 is delivered with a simple operating program compliant with EN 54. This program contains all necessary
standard parameters required for operating the control panel. Object-specific changes can be programmed with SecuriFire
Studio and transferred to the control panel.
A wizard developed specifically for SecuriFire 500 is available which provides guidance for fast commissioning in 8 steps. The
“EasyConfig SecuriFire 500” wizard is integrated in SecuriFire Studio.
6.2
SecuriLine eXtended addressable loop
The following steps are performed with the SecuriFire 500 control panel and SecuriFire Studio: electrics check and read-out of
the addressable loop, parameterisation and addressing of individual participants, loading the addressable loop data to the
control panels.
When checking the electrics of an installed addressable loop without SecuriFire 500 control panel, the “SecuriLine
Test
Board”
STB 01X testing device is used.
6.3
Object-specific texts
Predefined default texts can be changed and new texts created with SecuriFire Studio. Country-specific regulations concern-
ing minimum texts must be observed.