10 Rev. 1.2 13/01/2021
TECHNICAL DATA:
- Transformer Power Supply : 230 Vac 50-60Hz 150W max.
- Central Power Supply : (12) 20 Vac 50/60Hz 150W max.
- Flashing light output : (12) 24 Vdc 4 W max.
- Emergency battery input: (12) 24 Vdc 7A/h max.
- Motor outputs : (12) 24 Vdc 2 x 70 W max.
- Electric lock output : (12) 24 Vdc 12W max.
- Power supply to photocells : (12) 24 Vdc 3 W max.
- Indicator light output : (12) 24 Vdc 3 W max.
- Operating temperature : -10
55 °C
- Radio receiver : see model
- Op. transmitters : 12-18 Bit - Rolling Code - Plus
-TX max codes in memory : 150 (CODE or PED CODE)
- Container dimensions : 240x190x110 mm.
- Protection rating : IP 56
TERMINAL BOARD CONNECTIONS:
CN1 :
1 : Power supply input ( 12 ) 20 Vac 150W max.
2 : Power supply input ( 12 ) 20 Vac 150W max.
3 : -Input + Emergency battery (12) 24 Vdc 1.2/7Ah max.
4 : Input - Emergency battery (12) 24 Vdc 1.2/7Ah max.
5 : Input + Solar Panel
6 : Flashing light (12) 24 Vdc 4W max.
7 : Output - Flashing light (12) 24 Vdc 4W max.
8 : Motor 1 (12) 24Vdc max. 70W.
9 : Output - Motor 1 (12) 24Vdc max. 70W.
10 : Motor 2 (12) 24Vdc max. 70W.
11 : Output - Motor 2 (12) 24Vdc max. 70W.
CN2 :
1 : Electric lock (12) 24 Vdc 12W.
2 : Electric lock output - (12) 24 Vdc 12W.
3 : Photocell Control and power (12) 24 Vdc 3W.
4 : Photocell Control and power supply - (12) 24 Vdc 3W.
5 : Indicator light (12) 24Vdc 3W.
6 : Indicator light output - (12) 24Vdc 3W.
7 : Open-Close push button control input (NA).
8 : Pedestrian push button input / Close (NA), DS AUX (NC).
9 : Common GND input.
10: Block Input (NC).
11: Safety device input (NC).
12: Motor 1 Opening Limit Switch Input (NC).
13: Motor 1 Closing Limit Switch Input (NC).
14: Common GND input.
15: Motor 2 Opening Limit Switch Input (NC).
16: Motor 2 Closing Limit Switch Input (NC).
17: Aerial earth input.
18: Aerial hot pole input.
OPERATING CHARACTERISTICS:
Automatic Operation:
By using both the radio control ( Menù A4 - DOT 2= ON ) and
the low voltage push button panel ( PUL ) to activate the gate,
the following functioning is obtained:
the first impulse commands the opening mechanism until the
motor time expires or the opening limit switch has been
reached. The second impulse commands gate closing.
If an impulse is sent before the motor time elapses or before
reaching one of the two limit switches, the control unit
inverts
motion both when opening and closing.
Step-by-step operation:
By using both the radio control ( Menù A4 - DOT 2= ON ) and
the low voltage push button panel ( PUL ) to activate the gate,
the following functioning is obtained:
the first impulse activates the opening mechanism until the
motor time expires or the opening limit switch is reached, the
second impulse closes the gate. If an impulse is sent before
the motor time expires or one of the two end runs are reached,
the control unit will
stop
both opening and closing movements.
An additional control re-starts motion in the opposite direction.
Automatic Closing :
The control unit closes the gate automatically without sending
additional commands.
The choice of this operating mode is described in the
instructions for setting the delay period.
Pedestrian Passage:
The control unit allows only Motor 1 to be activated using either
the radio control ( Menù A5 - DOT 2= ON ) or the push button
panel ( PED ), for the programmed time ( Menù A7 - DOT 2=
ON ).
Single door:
Despite being used with a 2-motor automation configuration,
the control unit, via the Pedestrian/Single Door button only
activates Motor 1, following the times programmed when
programming the motor’s times.
Block Input:
The control unit allows the blocking button connection (NC).
Tripping during any operating phase of the control unit causes
movement to stop immediately. A further movement control will
be valid as long as the block input has been deactivated and, in
any case, the control unit will carry out the automatism opening
phase.
Jumper this input if not used.
Safety Device DS 1:
The control unit allows Photocells to be powered and
connected in accordance with directive EN 12453.
If the device trips during opening, it is ignored. If it trips during
closing, gate motion is reversed.
The control unit compulsorily requires the use of photocells,
connected to dedicated inputs, otherwise the unit is not
enabled for operation.
Safety Device DS 2 (Input BL):
Once duly configured, the control unit enables you to connect a
Safety Device 2 as an alternative to using the Block (NC) input,
in accordance with directive EN 12453.
If the device trips during opening, the gate stops momentarily.
Once freed, the control unit continues the opening phase. If the
device trips during closing, gate motion is reversed.
Opening and Closing Limit Switch:
The control unit allows distinct Opening and Closing Limit
Switch connection for each Motor (NC). When it is triggered
during the respective operating phases, movement of each
relative motor stops immediately.
Warning: Connect the limit switch, if applicable. Do not
jumper inputs FA1, FC1, FA2, FC2 in the terminal board.
Motor Power and Speed adjustment:
The
electronic control unit is equipped with a VR2 “VEL”
trimmer to adjust motor Power and Speed, fully managed by
the microprocessor. The adjustment can be made within a
range of 50% and 100% of the Maximum Power.
Warning: You will need to repeat the teach-in phase if
you wish to adjust the VR2 trimmer as operation and
deceleration times may be affected.
Obstacle detection:
The electronic control unit is equipped with a VR3 “SENS”
trimmer to adjust the Counter Power required to detect the
obstacle, fully managed by the microprocessor.
The adjustment can be made by setting a time interval between
a minimum of 0.1 seconds and a maximum of 3 seconds.