background image

4. 

OPERATION

4.1.   AC or DC voltage testing (fig 3) 

  

WARNING! To reduce risk of electric shock, DO NOT attempt to measure voltages  

 

higher than 1000V. 

 

The measurement ranges dC voltage are 200mV, 2V, 20V, 200V and 1000V. 

 

The measurement ranges AC voltage are 2V, 20V, 200V and 750V. 

 

Select the range appropriate to the expected reading.

 

If the voltage to be measured is unknown, use the maximum measurement position 

 

(1000V dC, 750V AC) and reduce the range, step by step until a satisfactory reading is  

 

obtained. Should the meter become overloaded, the lCd will display “1”. This indicates that  

 

a higher range must be selected. 

 

In each range, the meter has an input impedance of approx 10M

Ω. 

This may give rise to 

 

measurement errors when dealing with high impedance circuits. 

 

If the circuit impedance is <= 10k

Ω, 

the error is negligible (0.1% or less). 

4.1.1. To measure dC or AC voltage, connect the meter as follows:

4.1.2. Insert the red test lead into the “V” terminal and the black test lead into the “COM” terminal. 

4.1.3. Set the rotary switch to an appropriate measurement position in        or         

4.1.4. Connect the test leads across the source being measured. The measured value will be 

 

displayed. When the measurement has been completed, disconnect the test leads from the  

 

circuit being tested. 

4.2.  DC Current testing (fig 4)

  

WARNING! Never attempt an in-circuit current measurement where the open circuit  

 

voltage between terminals and ground is greater than 250V. If the fuse burns out 

 

during measurement, the meter may be damaged and the user may be injured. Always  

 

use correct terminals, function and range for the measurement. 

 

When the test leads are connected to the current terminals, DO NOT parallel them  

 

across any circuit. 

 

The measurement ranges for dC current are 200.0mA and 10.00A.

4.2.1. To measure dC current, use the following procedure:

4.2.2. Turn off/disconnect power to the circuit, discharge all high voltage capacitors. 

4.2.3. Insert the red test lead into the mA or 10A terminal and the black test lead into the COM  

 

terminal.

4.2.4. Set the rotary switch to an appropriate measurement position in         . If the current to be 

 

measured is unknown, use the maximum measurement position (10A) and the 10A terminal,  

 

then reduce the range step by step until a satisfactory reading is obtained. 

4.2.5. Break the current path to be tested, connect the red test lead to the positive side of the  

 

break and the black test lead to the negative side of the break (i.e. connect the meter in  

 

series).

4.2.6. Turn on/reconnect power to the circuit. The measured value is shown on the display. 

 

When the measurement has been completed, disconnect the test leads from the circuit being  

 

tested.

Note: Within the 10A range, the meter must not be used for a period of greater than 10 seconds  

 

more than once in any 15mins.

4.3.  Resistance testing (fig 5)

  

WARNING! To avoid damage to the meter and/or the devices being tested, disconnect  

 

circuit power and discharge all the high-voltage capacitors before measuring    

 

resistance.

 

Never attempt an in-circuit current measurement where the open circuit voltage  

 

between terminals and ground is greater than 60V DC or 30V AC rms. 

 

The measurement ranges for resistance are: 200

, 2k

, 20k

, 200k

, 2M

 

and 20M

Ω. 

4.3.1. To measure resistance, connect the meter as follows:
4.3.2. Insert the red test lead into the 

Ω 

terminal and the black test lead into the COM terminal.

4.3.3. Set the rotary switch to an appropriate measurement position in 

Ω.

4.3.4. Connect the test leads across the object being measured. The measured value will be 

 

displayed.  

 

Note: The test leads themselves can add 0.1-0.2

Ω 

to the resistance measurement. To obtain  

 

a precision reading in the low-resistance range (i.e. 200

Ω, 

short-circuit the input terminals  

 

using the test leads beforehand and record the measured resistance as 

x

. Then measure the  

 

resistance of the object under test and record this value as 

y

 

 

 

 

y – x = 

Correct value of resistance 

 
 

If the resistance reading 

≥ 

0.5

Ω 

in the short circuit condition, the test leads may be loose or  

 

damaged. If damaged, replace immediately with suitable leads from your authorised Sealey  

 

dealer. 

 

For high resistance (>1M

Ω)

 several seconds may be required to obtain a stable reading and  

 

it is recommended that you use short test leads. 

 

Where there is no input, the meter displays “1”.

 

When resistance measurement has been completed, disconnect the test leads from the  

 

circuit being tested. 

Note: During any of the following testing procedures, the data hold function can be employed.  

 

When the “

HOLD” button (see fig 1.2) is pressed, data hold is activated and the value 

 

displayed at that instant on the LCD is held until the 

HOLD button is pressed again, at which  

 

point the LCD once more displays the current measured value.  

Fig 3

Fig 4

Fig 5

 TA200      Issue No: 3 - 19/12/11

Original Language Version

Summary of Contents for TA200

Page 1: ... meter terminals When the scale of the value to be measured is unknown set the selector to the highest range available Before rotating the rotary switch to change functions disconnect test leads from the circuit under test WARNING Never perform resistance measurements on live circuits Always be careful when working with voltages above 60Vdc or 30Vac rms Keep your fingers behind the probe guards wh...

Page 2: ...ates an AC voltage or current The displayed value is the mean value Indicates a negative reading Diode test Continuity buzzer is on Data hold function is active Indicates the requirement for test leads to be connected Ω Ohm The unit of resistance kΩ kilohm 1x103 or 1000 ohms MΩ Megaohm 1x106 or 1 000 000 ohms V Volts The unit of voltage mV Millivolt 1x10 3 or 0 001 volts A Amperes amps The unit of...

Page 3: ...nt path to be tested connect the red test lead to the positive side of the break and the black test lead to the negative side of the break i e connect the meter in series 4 2 6 Turn on reconnect power to the circuit The measured value is shown on the display When the measurement has been completed disconnect the test leads from the circuit being tested Note Within the 10A range the meter must not ...

Page 4: ... tested is open Open circuit voltage is approx 2 7V When continuity testing has been completed disconnect the connection between the testing leads and the circuit under test 4 6 Dwell testing fig 7 4 6 1 This function can be used to test the dwell of the cut off switch points or electronic of an ignition system 4 6 1 1 Turn the rotary switch to the appropriate setting within the DWELL function are...

Page 5: ...cloth and mild detergent DO NOT use abrasives or solvents 5 1 2 Clean the terminals with a cotton bud and mild detergent to prevent the build up of dirt moisture in the terminals which may affect readings 5 1 3 Turn the meter off when not in use and remove the battery if the meter is not to be used for some time 5 2 To replace the fuses 5 2 1 Turn the meter off and disconnect any leads equipment f...

Page 6: ... 5 Tach rotation speed testing Input amplitude 10V in direct impulse 0 5mS in width Input amplitude 10V in direct impulse 0 5mS in width Maximum tach 10000 RPM displayed as RPM x10 Environmental Protection Recycle unwanted materials instead of disposing of them as waste All tools accessories and packaging should be sorted taken to a recycle centre and disposed of in a manner which is compatible wi...

Reviews: