25
© Sealevel Systems, Inc. eI/O Manual | SL9221 01/2023
If your eI/O module is set to a different subnet, you will need to type in the IP address into the IP Address
field displayed in MaxSSD and press Enter. MaxSSD will try to open port 502 on that address. When the
connection succeeds, it will display the “SeaIO Configuration” tab.
If no IP address is shown and your eI/O module is on the same subnet as the MaxSSD computer,
review the previous Hardware Configuration section or proceed to the Troubleshooting section at
the end of this manual.
SEAI/O CONFIGURATION TAB
Once the host computer is configured correctly, the “SeaI/O Configuration” tab becomes available. Before
communicating with an eI/O module, the configuration utility must determine if there is an I/O module, and
if so, what type of module it is. This is the purpose of the Get operation.
The eI/O modules will respond to any Slave ID, so just use the default.
Click the “Get SeaIO Module Settings” button. After a short delay, the information for that I/O module should
be displayed. If no information appears, verify that the host settings are correct and make changes if
necessary.