![SeaLevel eI/O 110E User Manual Download Page 11](http://html1.mh-extra.com/html/sealevel/ei-o-110e/ei-o-110e_user-manual_1223863011.webp)
11
© Sealevel Systems, Inc. eI/O Manual | SL9221 01/2023
eI/O Configurations & Specifications
110 SERIES – 4 OPTICALLY ISOLATED INPUTS/4 FORM A REED RELAY OUTPUTS
eI/O-110 modules provide 4 optically isolated inputs and 4 Form A Reed Relay outputs. Inputs can range
from 5-30VDC, while the Form A Reed Relays provide long life switch closures that are well suited for low
current applications. Each pair of inputs shares a common and field wiring is simplified via 3.5mm field
removable terminal blocks.
Do not connect protective earthing or protective bonding conductor wiring of any equipment to relay
contact outputs.
*Minimum hardware requirements
Inputs
Type
4 non-polarized optically isolated
inputs
Voltage Range
5-30VDC non-polarized
Isolation
2500VAC RMS / 3500VDC
Input Resistance
6.2K Ohms in series
Outputs
Type
4 SPST Form A Reed Relays
Contact Max Power
10W
Switching Voltage Max DC /
Peak AC Resistive
60VDC / 42VAC
Switching Current Max DC /
Peak AC Resistive
500mA
Life Expectancy – Typical
(Signal Level 1V, 10mA)
100 million ops.
Relay Max Operate Time,
including Bounce*
1ms
Relay Max Release Time*
0.2ms