SDMO VERSO 50 Instruction Manual Download Page 21

 
VERSO 50_v1.0.27_EN                                        33502027401_3_1                                                  page 19/24 

2- 7  M6 - EJPT setup 

It permits to activate the remote start if the inputs J4.4 is closed to negative. In this case, after a “Start delay” time, the remote start 
output is activated and, when the generator is within the limits, after “KG delay” the mains contactor is opened and the generator 
contactor is closed. 
When the input is open, if the mains is present the load is passed to the mains (opening of KG and closure of KR) then, after the 
cooling time, the remote start output is removed. 
If an alarm about the generator occurs, the management follows the programmation of parameter "E - No KR with EJPT": 

a)  If No KR with EJPT is set to Off: KG is opened and the load passes to the mains, with closure of KR. The remote start 

output remains active (if the active alarm is not set for genset stopping). 

b)  If No KR with EJPT is set to On: KG is opened but the load is not passed to the mains. The remote start output remains 

active (if the active alarm is not set for genset stopping). 

 

POS. 

NAME 

DESCRIPTION 

RANGE OF 

VALUES 

DEFAULT 

SETTINGS 

EJPT Enable 

If ON the function is enabled, if OFF the function is disabled. 

On/Off 

On 

Start delay 

It is the delay time that elapses when the input J4.4 closes to 
negative before the activation of the remote start output. 

0-59 [min] 

KG delay 

It is the delay time that elapses after the starting of the generator 
before the opening of KR and the closure of KG. 

0-59 [min] 

EJPT 2 input 

Function disabled in the VERSO 50 with only 1 input. 

On/Off 

Off 

No KR with EJPT 

If ON, when EJPT  mode is active (remote start input active), the 
mains contactor opens and it’s not possible to close it also if the 
generator is stopped by an alarm. 

On/Off 

Off 

Off delay 

It is the delay time during which the EJPT signal must be disabled to 
permit the stopping of the generator and the switchin on the mains. 

0-59 [s] 

10 

 

2- 8  M7 - Counters 

 

POS. 

NAME 

DESCRIPTION 

RANGE OF 

VALUES 

DEFAULT 

SETTINGS 

Run hours 

Here you can set a value of the work hours, then confirm the 
parameter D to set the actual work hours to this value. 

0-999999 [h] 

KG hours 

Here you can set a value of the work hours  with KG closed, then 
confirm the parameter D to set the actual work hours with KG closed 
to this value.

 

0-999999 [h] 

KR hours 

Here you can set a value of the hours with KR closed, then confirm 
the parameter D to set the actual hours with KR closed to this value.

 

0-999999 [h] 

Counter reset 

Confirm this parameter to set the values at parameters A, B and C. 

OK 

 

2- 9  M8 - Measures 

The measures setup allows to adjust the measured values for genset and mains voltages. For each measure it’s possible to set an 
offset with 0.1V.  

POS. 

NAME 

RANGE OF VALUES 

DEFAULT SETTINGS 

Offset VRG 

-100 +100 (V/10) 

Offset VSG 

-100 +100 (V/10)

 

Offset VTG 

-100 +100 (V/10)

 

Offset VRM 

-100 +100 (V/10) 

Offset VSM 

-100 +100 (V/10)

 

Offset VTM 

-100 +100 (V/10)

 

 
“G”=Generator, “M”=Mains 
 
 
 
 
 
 
 
 
 
 
                                                             Offset        Adjusted value 
 
 

Summary of Contents for VERSO 50

Page 1: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 1 24 VERSO 50 Instructions Manual Release 1 0 27 33502027401_3_1...

Page 2: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 2 24...

Page 3: ...ains stats 9 1 8 3 Generator 9 1 8 4 Generator stats 9 1 8 5 Hours 9 1 8 6 Events log 9 1 8 7 Clock and warranty 9 1 8 8 I O Monitor 10 1 8 9 Info page 10 1 8 10 System data 10 1 8 11 Logo page 10 2 P...

Page 4: ...e of fixation The panel must be fixed on the wall like the picture opposite with appropriate material Be careful there are 3 meters length cable between the genset control panel and the ATS Section of...

Page 5: ...rior notice Technical data and descriptions in the documentation are accurate to the best of our knowledge but no liabilities for errors omissions or contingencies arising there from are accepted A ci...

Page 6: ...C 70 C electric 30 C 70 C display 40 C 80 C storage DISPLAY 128x64 px 66x33mm DIGITAL INPUTS Number 1 STATIC OUTPUTS Number 1 CONTACTORS RELAYS Number 2 Type of contacts 1x N O genset contactor 1x N C...

Page 7: ...that the connections strictly comply with the wiring diagram below NOTE The remote start output is a positive If you want to use a negative instead of a positive it s possible to use an external relay...

Page 8: ...put NO 1 5 Genset voltage phase 1 1 6 Genset voltage phase 2 1 7 Genset voltage phase 3 1 8 Neutral J5 Supply and Outputs 5 1 Battery negative 5 2 Battery positive 5 3 Common positive for remote start...

Page 9: ...tivated to test the genset for a programmable time Test duration can be programmed inside M3 Test setup parameter M When the test is finish automatically the controller returns in MAN mode and the tes...

Page 10: ...s present J KR Key control to deactivate the remote start output only in manual mode keeping and releasing quickly the button the remote start output is removed immediately while keeping pressed the b...

Page 11: ...rator A L1 L2 Vac voltage B L2 L3 Vac voltage C L3 L1 Vac voltage D L1 line voltage E L2 line voltage F L3 line voltage G Generator frequency 1 8 4 Generator stats A Maximum value measured on the L1 l...

Page 12: ...T and the 3 outputs J1 2 KR J1 4 KG and J5 4 Remote start output 1 8 9 Info page This page contains the contacts data of the manufacturer web address telephone number and address 1 8 10 System data Th...

Page 13: ...one alarm active Pressing the HELP button you directly go to the active alarms page With the arrows you can select the menu Once selected the desired menu press the i button to confirm and enter or pr...

Page 14: ...remote start output in automatic mode 0 100 90 90 G KR delay You can set a delay time for the closure of the mains contactor This time starts from when the VERSO 50 opens the generator contactor soft...

Page 15: ...0 s 1 1 H GE Ok delay It is the delay time over which if the voltage and frequency are within limits parameters B C E F the generator is considered stable and its contactor is closed 0 9999 s 5 5 I KG...

Page 16: ...ou set the minute of test starting 0 59 0 Also you can set some parameters that are in common for the two tests POS NAME DESCRIPTION RANGE OF VALUES DEFAULT SETTINGS M Test lenght You set the length t...

Page 17: ...events occurs 0 255 s 60 C Return to default It is the time after which the controller automatically returns to the standby page Mains 1 if no buttons are pressed Off 250 s Off D Contrast To set the...

Page 18: ...ocks the alternator setup If you enter the code correctly to 50 the alternator setup is completely unlocked If you enter a wrong code the menu is locked 50 C Test password Enter the password that lock...

Page 19: ...the parameters from D to L in the configuration of the alarm selected at parameter A D Activation It permits to choose when the alarm condition must be verified and make the alarm appear Always always...

Page 20: ...generator Frequency values are under the programmed limits 2 1202 High frequency generator Frequency values are over the programmed limits 3 1203 Low voltage generator Voltage values are under the pr...

Page 21: ...arting of the generator before the opening of KR and the closure of KG 0 59 min 0 D EJPT 2 input Function disabled in the VERSO 50 with only 1 input On Off Off E No KR with EJPT If ON when EJPT mode i...

Page 22: ...3 PANELS ELECTRICAL DRAWINGS 3 1 Single Phase 40A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 20 24...

Page 23: ...3 2 Single Phase 100A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 21 24...

Page 24: ...3 3 Three Phase 25A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 22 24...

Reviews: