VERSO 50_v1.0.27_EN                                        33502027401_3_1                                                  page 17/24 

2- 6  M5 - Alarms list 

You will see a general screen for the setup of the alarms, composed by 4 pages. In the first page, select and confirm the parameter 
“a” to choose the code of the alarm. In the upper part of the screen you will see the name of the correspondant alarm. Then modify 
the parameters from “d” to “l” as you prefer. Return then to the first page and confirm the parameter “c” to save the modifications. 
 
 
 
 
 
 
 
 
 
 
 
For every alarm, you can program all the following parameters: 
 

POS. 

NAME 

DESCRIPTION 

RANGE 

Alarm code 

Select this parameter to choose the alarm that you want to set. All the parameters in the 
next pages refer to the alarm selected in this parameter. In the upper part of the screen 
you will see also the name corresponding to the code that you are selecting. 

Category of 

the alarm 

Not selectable parameter. 

Save alarm 

Parameter that has to be confirmed with the “i” button to save all the parameters from D to 
L in the configuration of the alarm selected at parameter A. 

Activation 

It permits to choose when the alarm condition must be verified and make the alarm 
appear: Always (always enabled), Run (active only with engine running) or Disabled 
(disabled). 

Always 

Run 

Disabled 

Delay 

Before the activation of the alarm, the cause must remain present for this time. 

0-255 [s] 

Retentive 

Choose if the alarm must be retentive (ON: the alarm indication remains on display until 
you press the reset button, even if the cause has disappeared) or not (OFF: the alarm 
indications disappears when the cause disappears). 

ON 

OFF 

Action 

Select the action in consequence of the activation of the alarm: Warning (only indication), 
Stop (the alarm stops the engine immediately) or Cooling (the alarms stops the engine 
with cooling). 

Warning 

Stop 

Cooling 

Siren 

Function not available. 

ON 

OFF 

SMS 

Function not available. 

ON 

OFF 

Global 1 

If On, the alarm activates the output set as Global alarm 1 (if present).

 

ON 

OFF 

Global KG 

If On, if the alarm is active KG cannot be closed.

 

ON 

OFF 

Global KR 

If On, if the alarm is active KR cannot be closed. 

ON 

OFF 

Summary of Contents for VERSO 50

Page 1: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 1 24 VERSO 50 Instructions Manual Release 1 0 27 33502027401_3_1...

Page 2: ...VERSO 50_v1 0 27_EN 33502027401_3_1 page 2 24...

Page 3: ...ains stats 9 1 8 3 Generator 9 1 8 4 Generator stats 9 1 8 5 Hours 9 1 8 6 Events log 9 1 8 7 Clock and warranty 9 1 8 8 I O Monitor 10 1 8 9 Info page 10 1 8 10 System data 10 1 8 11 Logo page 10 2 P...

Page 4: ...e of fixation The panel must be fixed on the wall like the picture opposite with appropriate material Be careful there are 3 meters length cable between the genset control panel and the ATS Section of...

Page 5: ...rior notice Technical data and descriptions in the documentation are accurate to the best of our knowledge but no liabilities for errors omissions or contingencies arising there from are accepted A ci...

Page 6: ...C 70 C electric 30 C 70 C display 40 C 80 C storage DISPLAY 128x64 px 66x33mm DIGITAL INPUTS Number 1 STATIC OUTPUTS Number 1 CONTACTORS RELAYS Number 2 Type of contacts 1x N O genset contactor 1x N C...

Page 7: ...that the connections strictly comply with the wiring diagram below NOTE The remote start output is a positive If you want to use a negative instead of a positive it s possible to use an external relay...

Page 8: ...put NO 1 5 Genset voltage phase 1 1 6 Genset voltage phase 2 1 7 Genset voltage phase 3 1 8 Neutral J5 Supply and Outputs 5 1 Battery negative 5 2 Battery positive 5 3 Common positive for remote start...

Page 9: ...tivated to test the genset for a programmable time Test duration can be programmed inside M3 Test setup parameter M When the test is finish automatically the controller returns in MAN mode and the tes...

Page 10: ...s present J KR Key control to deactivate the remote start output only in manual mode keeping and releasing quickly the button the remote start output is removed immediately while keeping pressed the b...

Page 11: ...rator A L1 L2 Vac voltage B L2 L3 Vac voltage C L3 L1 Vac voltage D L1 line voltage E L2 line voltage F L3 line voltage G Generator frequency 1 8 4 Generator stats A Maximum value measured on the L1 l...

Page 12: ...T and the 3 outputs J1 2 KR J1 4 KG and J5 4 Remote start output 1 8 9 Info page This page contains the contacts data of the manufacturer web address telephone number and address 1 8 10 System data Th...

Page 13: ...one alarm active Pressing the HELP button you directly go to the active alarms page With the arrows you can select the menu Once selected the desired menu press the i button to confirm and enter or pr...

Page 14: ...remote start output in automatic mode 0 100 90 90 G KR delay You can set a delay time for the closure of the mains contactor This time starts from when the VERSO 50 opens the generator contactor soft...

Page 15: ...0 s 1 1 H GE Ok delay It is the delay time over which if the voltage and frequency are within limits parameters B C E F the generator is considered stable and its contactor is closed 0 9999 s 5 5 I KG...

Page 16: ...ou set the minute of test starting 0 59 0 Also you can set some parameters that are in common for the two tests POS NAME DESCRIPTION RANGE OF VALUES DEFAULT SETTINGS M Test lenght You set the length t...

Page 17: ...events occurs 0 255 s 60 C Return to default It is the time after which the controller automatically returns to the standby page Mains 1 if no buttons are pressed Off 250 s Off D Contrast To set the...

Page 18: ...ocks the alternator setup If you enter the code correctly to 50 the alternator setup is completely unlocked If you enter a wrong code the menu is locked 50 C Test password Enter the password that lock...

Page 19: ...the parameters from D to L in the configuration of the alarm selected at parameter A D Activation It permits to choose when the alarm condition must be verified and make the alarm appear Always always...

Page 20: ...generator Frequency values are under the programmed limits 2 1202 High frequency generator Frequency values are over the programmed limits 3 1203 Low voltage generator Voltage values are under the pr...

Page 21: ...arting of the generator before the opening of KR and the closure of KG 0 59 min 0 D EJPT 2 input Function disabled in the VERSO 50 with only 1 input On Off Off E No KR with EJPT If ON when EJPT mode i...

Page 22: ...3 PANELS ELECTRICAL DRAWINGS 3 1 Single Phase 40A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 20 24...

Page 23: ...3 2 Single Phase 100A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 21 24...

Page 24: ...3 3 Three Phase 25A VERSO 50_v1 0 27_EN doc 33502027401_3_1 Page 22 24...

Reviews: