I&O manual

24

Spot check content according to the main unit model wired controller:

8.4 Query display

    Press the “

” or “

” key of wire controller to adjust the main unit 

serial number can query 16 sets main units’ status information from 
#0

#15. Press “     ” or “    ” to adjust the spot check sequence 

number of one main unit then can query all the status information of 
this unit. 

No.

Spot inspection item
Standby: ODU address (L88) + number of on-line units
(R88),
On: display frequency
Defrosting: dF and operating frequency flash alternately
at 1s intervals
In case of Pb protection, Pb and operating frequency
flash alternately at 1s intervals

1

0.xx

ODU address

2

1.xx

ODU Hp

3

2.xx

Number of ODUs (Main unit included)

4

3.xx

T4 capacity revision

5

4.xx

Operation modes (8 OFF, 0 Standby, 1 Cooling, and 2
Heating)

6

5.xx

Fan Speed 1

7

6.xx

Fan Speed 2

8

7.xx

T3

9

8.xx

T4

10

9.xx

T5

11

10.xx Taf1

12

11.xx Taf2

13

12.xx Tw

14

t.xx

Twi unit water inlet (displays to decimal places)

15

14.xx Two unit water outlet

16

15.xx Tz general cold water leaving temperature

17

16.xx THeatR heat recovery sensor temperature

18

17.xx Air discharge 1

19

18.xx Air discharge 2

20

19.xx Heat sink temperature 1

21

20.xx Heat sink temperature 2

22

21.xx Air discharge superheat degree DSH

23

22.xx Current of compressor A

24

23.xx Current of Compressor B

25

24.xx Water pump current

26

25.xx Electronic expansion valve 1 opening (/4)

27

26.xx Electronic expansion valve 2 opening (/4)

28

27.xx High pressure

29

L.xx

Low pressure (displays to decimal places)

30

29.xx Air return superheat degree

31

30.xx Air return temperature

32

31.xx Mute selection

33

32.xx Static pressure selection

34

33.xx DC voltage A (reserved)

35

34.xx DC voltage B (reserved)

36

35.xx Last fault

37

36.xx

Limit frequency No. (0: no limits; 1: T4 limit frequency; 2:
voltage limit frequency; 3: air discharge limit frequency;
4: low voltage ratio; 5: instant limit frequency; 6: current
limit frequency; 7: voltage limit frequency; 8: pressure
ratio and capacity demand adjusting; 9: cooling low
pressure limit frequency)

38

37.xx

Defrosting process status (the first digit: T4 selection
solution; the second digit: scheme's range; the third and
fourth digits as a whole indicates the defrosting time)

39

38.xx

E-direction failure: 1 indicates failure, and 0 indicates no
failure

40

39.xx Defrosting scheme

41

40.xx Initial frequency

42

41.xx Tc

43

42.xx Te

44

43.xx ----

0

8.2 Ordinary displayed data

a. Ordinary displayed data are displayed in all display pages.

b. If the unit system is under running state, i.e. one or more than 
one Modular unit is under running operation, there will be a 
dynamic display of         . If the system is under OFF state, there 
is no display.

c. If the communication with the main unit Modular unit is fail, it 
displays   E2         

d. If it is under the host computer network control, 

Net

Net

 displays, 

otherwise there is no display.

e. If it is under wired controller locked or button locked state, it 
displays       the lock mark. There will be no display after the lock 
is unlocked. 

8.3 Treatment of display data

The data display area is divided into Up area and Down area, 
with two groups of two-digit half 7-segment digital display, 
respectively.

a.Temperature display
Temperature display is used for displaying the total outlet water 
temperature of unit system, outlet water temperature ,condenser 
pipe temperature T3A of system A, condenser pipe temperature 
T3B of system B, outdoor environmental temperature T4, 
anti-freezing temperature T6 and setting temperature Ts, with 
allowable data display scope -15

℃~

70

. If the temperature is 

higher than 70

, it is displayed as 70

. If there is no effective 

date, it displays “— —” and indication point 

 is on.

b. Current display 
Current display is used for displaying Modular unit system A 
compressor current IA or system B compressor current IB, with 
allowable display scope 0A~99A. If it is higher than 99A, it is 
displayed as 99A. If there is no effective date, it displays “— —” 
and indication point 

A

 is on.

c. Failure display
It is used for displaying the total failure warning date of unit or 
that of Modular unit, with failure display scope E0~EF, E 
indicating failure, 0~F indicating failure code. “E-“ is displayed 
when there is no failure and indication point 

is on at the same 

time.

d. Protection display
It is used for displaying the total system protection data of unit or 
the system protection data of Modular unit, with protection 
display scope P0~PF, P indicating system protection, 0~F 
indicating protection code. “P-“ is displayed when there is no 
failure .

e. Unit number display
It is used for displaying the address number of the currently 
selected Modular unit, with display scope 0~15 and indication 
point 

#

 is on at the same time.

f. Display of online unit number and startup unit number
They are used for displaying the total online Modular units of the 
whole unit system and the number of the Modular unit under 
running state, respectively, with display scope 0~16.
Any time when the spot check page is entered to display or 
change Modular unit, it is needed to wait for the up-to-date data 
of the Modular unit received and selected by wired controller. 
Before receiving the data, the wired controller only displays 
“——” on the data display Down area, and the Up area displays 
the address number of the Modular unit. No page can be turned, 
which continues until the wired controller receives the 
communication data of this Modular unit.

Summary of Contents for SCV-xxEA

Page 1: ...AIR COOLED MODULAR CHILLER UNIT INSTALLATION AND USER MANUAL SCV xxEA AIR CONDITIONING...

Page 2: ...Original instructions...

Page 3: ...A Temperature testing components of total water outlet 1 1 1 1 Purpose Shape Qty Unit transformer Installation Operation Manual Use for installation only need for setting the main module Installation...

Page 4: ...2 SCV 600EA NO NAME 1 2 3 4 5 6 7 Air outlet Top cover Air inlet Electric control box Condenser Compressor Evaporator NO NAME 8 9 Water outlet Water intlet 1 2 8 7 9 4 6 3 5...

Page 5: ...matching and thus actually realizing optimal energy saving operation The product is Modularized unit and parallel connection of 16 modules can be realized at most so the user can adopt module combina...

Page 6: ...as unsorted municipal waste Collection of such waste separately for special treatment is necessary Keep far away from high frequency equipment Keep away from the following places a place where it is f...

Page 7: ...ticide Failure to observe could cause the chemicals to become deposited in the unit which could endanger the health of those who are hypersensitive to chemicals Do not place appliances which produce o...

Page 8: ...tend below frozen soil layer The foundation of the unit should not be connected to the foundation of the building to avoid affecting the people due to transfer of noise and vibration The base of the u...

Page 9: ...han the static pressure outside the fan The space between the unit and sunk fence or Persian blinds should also meet the requirement of the minimum installation space of the unit 3 3 1 3 If the unit n...

Page 10: ...n foundation of the unit unit mm 80 Cement mortar Concrete Drainage channel Fig 3 6 3 6 Installation of damping devices 3 6 1 Damping devices must be provided between the unit and its foundation By me...

Page 11: ...pes a All chilled water pipelines should be thoroughly flushed to be free of any impurity before the unit is operated Any impurity should not be flushed to or into the heat exchanger b Water must ente...

Page 12: ...eck valve Automatic discharge valve Symbol explanation Fig 4 1 Main unit Expansion tank Water replenishing Dirt discharge valve Differential pressure by pass valve Drain valve Two way valve Three way...

Page 13: ...tance pipe elbow and three way resistance two way resistance or three way resistance as well as filter resistance H4 the longest terminal resistance 4 7 2 Installation the pump a The pump should be in...

Page 14: ...ne must be consistent with the direction of arrow on the controller The connection terminal should be located where wiring connectioncan be easily done 4 9 4 Pay attention to the following items when...

Page 15: ...ngle module water system pipeline Fig 4 5 SCV 300EA Fig 4 6 SCV 600EA Water inlet Water outlet Total water outlet temperature sensor Electric control box Electric control box Water inlet Water outlet...

Page 16: ...items are determined The wired controller is 500m away from the outdoor unit 25 Q 50 50 Q 80 80 Q 130 135 Q 210 210 Q 325 325 Q 510 510 Q 740 740 Q 960 DN40 DN50 DN65 DN80 DN100 DN125 DN150 DN200 4 11...

Page 17: ...electromagnetic interference thus leading to failure of the unit and its controller and even damages to them 5 3 10 All weak current wires led to the electric box must apply shielded wires which must...

Page 18: ...d N Step 7 Phase sequences must be consistent when the wires of the main power Step 8 The main power should be located out of easy reach of non professional maintenance personnel to avoid mal operatio...

Page 19: ...hen the subordinate unit suffer fault of temperature sensor the unit will be shut down but other subordinate units will not be affected Taf1 Shell and tube low temperature ant freeze sensor1 fault cod...

Page 20: ...l modules stop operating 3 In case of shutdown under the pump mode the pump can be directly shut down CN30 Input of three phase four wire power supply fault code E1 Three phases A B and C of power sup...

Page 21: ...for the main unit Spot check The operating status of outdoor system can be observed through spot check and specific display contents are as shown in the following figure Display contents of operating...

Page 22: ...ed in Table 7 1 6 2 Check item table after installation Checking item Description Yes No Whether installing site is meet for requirements Whether water system is meeting for requirements Whether elect...

Page 23: ...ler must be connected according to electric control schematic diagram or the faults caused by water breaking while the unit is in operation should be the user s responsibility Do not re start the unit...

Page 24: ...ons 1 Plug and play system 2 RS 485 TS232 Standard serial communication port Turn on the unit Press MENU key to set the intended mode Power up to module unit and initially deliver power to wired contr...

Page 25: ...ir suction pressure Check ambient temperature around it Discharge the excessive refrigerant Charge sufficient refrigerant to the system Check fan rotating direction Reason about remove air short circu...

Page 26: ...re Replace a new compressor Replace damaged assembly Control circuit without power though Check the wring of control system Hi voltage or lo voltage protection Reference to mention in above the parts...

Page 27: ...2 error Communication error between main control board and wired controller Power phase sequence error P1 P0 1E0 E1 E2 E3 E4 E5 E7 E8 E9 1Eb 1Ed 2Ed 1P6 2P6 EC EF EH EP EU 2E0 3E0 P4 P5 P9 Condenser h...

Page 28: ...ll be a dynamic display of If the system is under OFF state there is no display c If the communication with the main unit Modular unit is fail it displays E2 d If it is under the host computer network...

Page 29: ...d check suction and discharge pressure Maintenance of main parts Close attention should be paid to the discharge and suction pressure during the running process Find out reasons and eliminate the fail...

Page 30: ...el connect the HEAT COOL port of the main unit s electric control box then connect the ON OFF signal provide by user to the HEAT COOL port of main unit as follows 0 electric control box ON OFF port ON...

Page 31: ...temperature of chilled water or hot water Inlet Outlet 6 check air temperature of air side heat exchanger Inlet Outlet 7 Check refrigerant suction temperature and superheating temperature Refrigerant...

Page 32: ...Outdoor temperature Compressor Air temperature of air side heat exchanger Temperature of chilled water or hot water Current of cooling water pump or hot water pump Dry bulb Wet bulb Indoor temperatur...

Page 33: ...etc High or low pressure switch freeze proof device water flow volume controller Overcurrent device power phase sequence device etc Standard heating input kW Heating rated current Notes the above dat...

Page 34: ...to water heat pump Brine to water heat pump For low temperature heat pumps parameters shall be declared for low temperature application Otherwise parameters shall be declared for medium temperature a...

Page 35: ...Kingdom 1 For heat pump space heaters and heat pump combination heaters the rated heat output Prated is equal to the design load for heating Pdesignh and the rated heat output of a supplementary heat...

Page 36: ...iary heater and pump is just for reference please follow the instructions of corresponding auxiliary heater products Please choose such accessory as power wire switch of auxiliary heater according to...

Page 37: ...iliary heater and pump is just for reference please follow the instructions of corresponding auxiliary heater products Please choose such accessory as power wire switch of auxiliary heater according t...

Page 38: ...unit is containing fluorinated gases included in the Kyoto protocol The maintenance and the liquidation must be carried out by qualified personnel Type of refrigerant R410A The composition of the cool...

Reviews: