background image

23

22

6. 

operation & maintenance

operation & user guide (Continued)

Before establishing the first fire, remove all labels or equipment parts located in the ash box or in the 

furnace. 

While building your first fire, keep the combustion rate at a moderate level to ensure that the sealant binds 

with the paint. all materials should be seasoned. 

please note:

 Before building a big fire, establish several fires. The curing process is necessary to ensure 

that the paint is not damaged and that the insert is well seasoned. do not overload the furnace. the 

optimum amount of fuel should not exceed one third of the insert volume. Before reloading, make sure 

that the fire has subsided. This will keep the fireplace from over-firing. 

Flow of air can be regulated by the air controls at the front of the unit (illustrated in diagram above).

Except for the short time required to build a fire, the fireplace door should be fully closed. If doors are left 

partly open, flue gas may be drawn out of the opening creating risks from both fire and smoke. 

establisHing tHe first fire

ignition instruCtions (continued)

After an extended time of non-use, it is recommended that the firebox be checked and cleaned by a 

professional to ensure there is no obstruction in the flue and no blocking of the manoeuvring members 

(damper) before ignition.

damper air Controls

The best way to control the fire is to completely close the primary air slide and to adjust the speed with 

the combustion air control. If the air supply seems sufficient you can partially open the primary air slide 

for a while. The more air you will supply into the stove, the more intense your fire will be, but with a shorter 

time of combustion. on the contrary, a reduced quantity of air would increase the combustion with less 

heat output.

Primary air slide

Door handle

Combustion air control 

6. 

operation & maintenance

important

Ventilation devices which operate with the fireplace on the same premises or on the premises which 

share the same ventilation shaft may not function properly.
Please ensure the air grate is never blocked.
During installation please allow for access to have the fireplace and the connecting shaft cleaned. 
If required, install cut-off and stifling devices.

reCommended fuel

This fireplace is designed for only wood fuel. Any fuel other than wood is strictly forbidden. 

As a general rule it is recommended; use dry, well-seasoned 

Hard wood

 with a 15% moisture content or 

less in order for the unit to burn effectively and avoid any tarring. the heating output of wood depends on 

the moisture percentage.

directly cUt
3 montHS  
6 montHS  
9 montHS  

75%
48%
37%
36% 

78%
62%
46%
38% 

33%
18%
16%
15% 

35%
27%
24%
24% 

1 year
1 1/2 year
2 yearS
2 1/2 yearS

C

C

l

l

C: Chunks l: logs

avEragE WooD Drying tiME BasED on MoisturE ContEnt

if the wood is piled up loosely, it will burn faster because the necessary oxygen for the combustion will 

easily reach every piece of wood. this piling is recommended if you want to heat over a short period of 

time. When the wood is piled more compact, it will burn slower because the oxygen won’t reach all the 

logs at the same time. this piling is recommended if you want to heat over a longer period of time.

it is ForBiDDEn to oPEratE this FirEBox With thE Door oPEn.

door:

 do not open the door too fast as this will create a suction of smoke inside the room.

atmospHeriC Conditions

Misty or foggy weather may possibly favour back-flow of the smoke, which may be a health hazard. In 

this case only use the fireplace as is necessary.

for safety reasons, assemblies of appliances and accessories not provided or recommended by axis or 

sculpt fireplaces are not permitted. unsuitable equipment may cause dysfunctions and disorder upon 

use.

eXtinguisHing tHe fire

 

Stop fuelling the fire and let it burn out. The fire should burn out without any constraints. Do not close the 

air slides before the fire is completely extinguished, otherwise it may release noxious gases. 

Caution:

 do not hang or install objects within 2m of the appliance. this includes paintings, photos, 

televisions, and any other combustible material.

Summary of Contents for AXIS I1000 IB ZERO CLEARANCE

Page 1: ...ALL GUIDE 4 ZERO CLEARANCE ASSEMBLY 5 install guide 6 OPERATION MAINTENANCE 7 test report 8 Warranty I1000 I1000DS IB ZERO CLEARANCE Installation User guide AXIS NOTICE TO INSTALLER These instructions must be left with the owner who should keep them for future use ...

Page 2: ... in order to become acquainted with the installation methods specific to your fireplace It is recommended that this fireplace be installed by a qualified and licensed trades professional You will find in this guide the answers to most of your questions should you require further assistance we recommend you contact your retailer Before igniting your fireplace for the first time please carefully rea...

Page 3: ...he distributor and manufacturer bears no liability to the interpretation of these instructions Copyright 2019 Sculpt Fireplaces Collection 2 SPECIFICATIONS AXIS I1000IB Single Sided Solid steel firebox with firebricks Up to 15 30 Squares 14 6kW 1 2g kg 66 Secure Swing door opening system 4 6m 200mm 250mm 300mm Recommended for well insulated homes 10 year firebrick 5 year firebox warranty 180kg Wid...

Page 4: ...losure must be made of a non combustible material to a height of 300mm above the appliance fascia and must extend to 100mm either side of the appliance fascia The internal wall studs of the appliance must also be made of a non combustible material IMPORTANT MANTEL SHELF Mantel shelf and mantel upright clearance was not tested and should be installed as per clause 3 4 1 3 b of AS NZS 2918 2018 A mi...

Page 5: ...rotector should extend 550mm in front of each fuel loading door and be placed centrally in the 1300mm width The appliance is required to be installed on 40mm high spacers inside the zero clearance box between the appliance and the base of the zero clearance box PLEASE NOTE A minimum 50mm air gap must be maintained around the outer triple skin flue skin in the ceiling of the enclosure 100MM non com...

Page 6: ...listed in this manual are recommendation only It is strongly recommended that the licensed trade professional who is performing the installation of this appliance completely read and comprehend all instructions in this manual prior to proceeding Sculpt Fireplaces Axis reserves the right to change these specifications without prior notice PLEASE READ PRIOR TO INSTALL ACCEPTABLE VARIANCE ALLOWANCE D...

Page 7: ...2 If a floor protector hearth is to be used position now refer to clearances pg 7 8 for a guide on the appropriate positioning to accompany clearances and the floor protector hearth Step 3 Position the appliance refer to clearances pg 7 8 for minimum requirements Step 4 Prior to proceeding ensure both the zero clearance firebox and hearth are fixed in position Step 5 Refer to Flue System Installat...

Page 8: ...arious functioning components of the appliance Insist on the wood quality on the need to light the fire correctly and have correct combustion in order to avoid all problems related to smoke emission in the room or blackened glass These installation instructions are an integral part of the appliance and should be kept indefinitely IF THE FIREPLACE IS SOLD THE MANUAL MUST ACCOMPANY THE UNIT commissi...

Page 9: ...ombustables 500mm NON COMBUSTIBLE STUD NON COMBUSTIBLE 42mm 100mm air gap 550mm min 4600mm from the hearth to the top of the flue 500mm NON COMBUSTIBLE 5 INSTALL GUIDE single sided AXIS I1000 bench NON COMBUSTIBLE BASE HEARTH roof cavity 50MM AIR GAP TO TRIPLE SKIN FLUE triple skin flue braces to support flue roof flashing WINDRIM cowl VENTED cover cone TRIPLE SKIN FLUE roof line interior roof Thi...

Page 10: ...3 Cut the ceiling penetration as required perform the same at the roof penetration Step 4 Frame the penetration with roofing material or timber as required Refer to minimum requirement for roof penetration AS NZS 2918 2018 Step 5 Flash the outer casing to the roof material with the appropriate approved flashing Step 6 If using an outer inner casing combination now install the inner casing ensuring...

Page 11: ...he paint will polymerise after several fires Do not scrub or clean the fireplace with any rough surface such as a sponge In the case of accidental scratches make several fires until the paint is cured at which time you can delicately clean the outside of the appliance with a hot sponge Do not scratch or rub the fireplace while it is lit It is recommended contact with the fireplace should be kept t...

Page 12: ...s or on the premises which share the same ventilation shaft may not function properly Please ensure the air grate is never blocked During installation please allow for access to have the fireplace and the connecting shaft cleaned If required install cut off and stifling devices RECOMMENDED FUEL This fireplace is designed for only wood fuel Any fuel other than wood is strictly forbidden As a genera...

Page 13: ...he wood stove CLEANING THE GLASS The window of the fireplace requires regular cleaning with specific products intended for this use The use of moist hard wood with a moisture content above 15 causes excessive creosote build up on the glass Once again we recommend only burning very dry hard wood We recommend waiting for the glass to cool before cleaning it The use of products that are too aggressiv...

Page 14: ...rt and where necessary cover glowing wood with sand Try to remove fuel from the hearth Do NOT use water to put out the fire as it may cause permanent damage Troubleshooting and course of action to put out the fireplace in the event of an emergency chimney fires continued Suggested course of action in case of chimney fires 1 Put out the fire by carefully removing the glowing logs and fully close th...

Page 15: ...or re installation of a replacement heater is not covered 9 All warranties are void if the unit is outside and exposed to the elements PERFORMANCE The performance of our fireplaces are given as an indication and comparison after testing under optimum conditions These values reported under standard conditions may be subject to variations if the installation and conditions of use are not equivalent ...

Page 16: ...ith a dynamic collection of designer fires Sculpt fireplace collection has strategically gathered not only award winning fireplace designs but also fireplaces that have been manufactured with high quality materials and the best raw steel that is built to last Our wood fire manufacturers integrate innovation technology environmental impact operational expertise and quality whilst holding design at ...

Page 17: ...32 1300 851 304 info sculptfireplaces com au PO Box 1232 Mornington VIC 3931 Edition 04 07 19 ...

Reviews: