SCS CTE701 Operating Instructions Manual Download Page 3

TB-9031

 Page 3 of 11

© 2022 DESCO INDUSTRIES INC

Employee Owned

SCS 

- 926 JR Industrial Drive, Sanford, NC 27332

East: (919) 718-0000 | West: (909) 627-9634 • Website: 

StaticControl.com

Installation

The CTE701 Verification Tester's 10-position DIP switch 

is used to configure its test limits for soft ground, metal 

ground, EMI, and operator.

Soft Ground

The soft ground resistance is configured with switches 

1-4. Pressing the SOFT GROUND pushbutton will result 

in a load with slightly lower resistance than the test limit.

Switch

Test Limit

1

2

3

4

1 gigohm

OFF

OFF

OFF

ON

400 megohms

OFF

OFF

ON

ON

100 megohms

OFF

ON

ON

ON

10 megohms

ON

ON

ON

ON

Metal Ground

The metal ground impedance is configured with 

switches 5-8. Pressing the HIGH METAL GROUND 

pushbutton will load 1 ohm higher than the configured 

test limit. Pressing the PASS METAL GROUND 

pushbutton will load 1 ohm less than the test limit. For 

example, if the monitor to be checked is set to 10 ohms, 

the Verification Tester will verify that it passes at 9 ohms 

and fails at 11 ohms.

Switch

Test Limit

5

6

7

8

1 ohm

ON

ON

ON

ON

2 ohms

OFF

ON

ON

ON

3 ohms

ON

OFF

ON

ON

4 ohms

OFF

OFF

ON

ON

5 ohms

ON

ON

OFF

ON

6 ohms

OFF

ON

OFF

ON

7 ohms

ON

OFF

OFF

ON

8 ohms

OFF

OFF

OFF

ON

9 ohms

ON

ON

ON

OFF

10 ohms

OFF

ON

ON

OFF

11 ohms

ON

OFF

ON

OFF

12 ohms

OFF

OFF

ON

OFF

13 ohms

ON

ON

OFF

OFF

14 ohms

OFF

ON

OFF

OFF

15 ohms

ON

OFF

OFF

OFF

16 ohms

OFF

OFF

OFF

OFF

EMI

The EMI high frequency signal is configured with switch 

9. The CTE701 Verification Tester provides two different 

levels of high frequency signal: elevated and normal. 

Pressing the HIGH EMI pushbutton will load a high 

signal level within its range. Pressing the LOW EMI 

pushbutton will load a low signal within its range. 

Switch

Signal Level

9

Elevated

ON

Normal

OFF

Wrist Strap

The wrist strap resistance is configured with switch 10. 

The CTE701 Verification Tester provides resistance 

of a certain value across the wrist strap terminal 

input in order to simulate a wrist strap. A good quality 

dual-wire wrist cord has a 1 megohm resistor in each 

of its conductors. The Verification Tester is designed 

to simulate dual-wire wrist straps with and without 

resistors. The 12 megohms setting simulates a wrist 

strap with two 1 megohm resistors in series. 

Switch

Test Limit

10

12 megohms

OFF

10 megohms

ON

Operation

Iron Man® Plus Workstation Monitor

CONFIGURING THE VERIFICATION TESTER

Configure the Verification Tester's DIP switch to the 

settings shown below. This will make its test limits 

match the factory default limits of the monitor.

VERIFYING THE OPERATOR CIRCUIT

1.  Use the black test lead to connect the Verification 

Tester to equipment ground. 

2.  Power the Verification Tester ON. 
3.  Use the 3.5 mm mono cable to connect the 

Verification Tester to the monitor's operator jack. 

The monitor's operator LED will illuminate red, and 

its alarm will sound. 

Summary of Contents for CTE701

Page 1: ...nds annual calibration of workstation monitors and the CTE701 Verification Tester The CTE701 Verification Tester meets ANSI ESD S20 20 and Compliance Verification ESD TR53 November 2022 The SCS CTE701 Verification Tester can be used with the following items Item Description 770067 WS Aware Monitor 770068 WS Aware Monitor CTC061 3 242 WW WS Aware Monitor CTC061 RT 242 WW WS Aware Monitor CTC062 RT ...

Page 2: ...operator circuit when pressed F Soft Ground Test Switch Simulates a MAT PASS condition on the monitor when pressed G Wrist Strap Test Switch Simulates a OPERATOR PASS condition on the monitor when pressed H Test Limit DIP Switch Configures the test limits on the CTE701 Verification Tester I High Metal Ground Test Switch Simulates a TOOL FAIL condition on the monitor when pressed J High EMI Test Sw...

Page 3: ...FF 14 ohms OFF ON OFF OFF 15 ohms ON OFF OFF OFF 16 ohms OFF OFF OFF OFF EMI The EMI high frequency signal is configured with switch 9 The CTE701 Verification Tester provides two different levels of high frequency signal elevated and normal Pressing the HIGH EMI pushbutton will load a high signal level within its range Pressing the LOW EMI pushbutton will load a low signal within its range Switch ...

Page 4: ...OLTAGE test switches simultaneously 6 Continue to press and hold the Verification Tester s WRIST STRAP test switch Simultaneously press and hold the Verification Tester s HIGH BODY VOLTAGE test switch The monitor s green operator LED will illuminate continuously its red LED will blink and an audible alarm will sound This verifies the operator circuit s high body voltage limit Figure 6 Pressing the...

Page 5: ...und 18 Set the variable DC power supply to 4 0 V The monitor s Iron LED should illuminate green and its audible alarm should stop 19 Disconnect the variable DC power supply from the monitor and ground Connect its positive terminal to ground and its negative terminal to the monitor s yellow alligator cord 20 Verify that the variable DC power supply is still set to 4 0 V The monitor s Iron LED shoul...

Page 6: ...e 12 Pressing the WRIST STRAP and HIGH BODY VOLTAGE test switches simultaneously 7 Disconnect the mono cable from the monitor VERIFYING THE MAT CIRCUIT 8 Connect the red test lead to red banana jack located at the top of the Verification Tester 9 Disconnect the monitor s white mat monitor cord from its worksurface mat and turn it over to expose its 10 mm snap 10 Clip the red test lead s mini grabb...

Page 7: ...ch The monitor s tool LED will illuminate red and its audible alarm will sound This verifies the tool circuit s impedance limit 20 Press and hold the Verification Tester s METAL GROUND PASS test switch Simultaneously press and hold the Verification Tester s EMI LOW test switch The monitor s tool LED will remain green and no audible alarm will sound This verifies the operator circuit s low EMI volt...

Page 8: ...s the tool circuit s impedance limit Figure 21 Pressing the METAL GROUND PASS test switch 5 Press and hold the Verification Tester s METAL GROUND FAIL test switch The monitor s tool LED will illuminate red and its audible alarm will sound This verifies the tool circuit s impedance limit Figure 22 Pressing the METAL GROUND FAIL test switch 6 Press and hold the Verification Tester s METAL GROUND PAS...

Page 9: ...necting the Verification Tester to the Ground Man Plus Workstation Monitor s operator jack Figure 26 Pressing the WRIST STRAP test switch Figure 27 Pressing the WRIST STRAP and LOW BODY VOLTAGE test switches simultaneously 4 Press and hold the Verification Tester s WRIST STRAP test switch The monitor s operator LED will illuminate green and its audible alarm will stop This verifies the operator ci...

Page 10: ...GROUND PASS test switch The monitor s tool LED will illuminate green and its audible alarm will stop This verifies the tool circuit s impedance limit 12 Press and hold the Verification Tester s METAL GROUND FAIL test switch The monitor s tool LED will illuminate red and its audible alarm will sound This verifies the tool circuit s impedance limit 13 Press and hold the Verification Tester s METAL G...

Page 11: ... Battery LED illuminates red Open the compartment located on the back of the tester to replace the battery The tester uses one 9V alkaline battery Ensure that the battery s polarities are oriented correctly to avoid possible circuit damage Specifications Operating Temperature 50 to 95 F 10 to 35 C Environmental Requirements Indoor use only at altitudes less than 6500 ft 2 km Maximum relative humid...