Installing the Detector
FV-40 Series Flame Detector
087-0056 REV F
33
Figure 4 shows the Tilt Mount Assembly with dimension in both millimeters
and inches.
Figure 4: Tilt Mount Assembly (dimensions in mm and inches)
➣
To install the Tilt Mount and Detector:
A.
Place the tilt mount in its designated location and secure it with four (4)
fasteners through four (4) holes 7 mm in diameter. Use the four (4)
screws and spring washers provided, or adequate hardware of your own
choosing.
Note:
Removing the detector for maintenance purpose does
not require the Tilt Mount to be removed).
B.
Unpack the detector.
C.
Place the detector with its conduit/cable entries pointing downwards on
the holding plate of the tilt mount. Secure the detector with
5
/
16
" 18 UNC
x 1" screw to the tilt mount.
D.
Release the Horizontal and Vertical Locking Screws using
3
/
16
" Hex Key
such that the detector can be rotated. Point the detector towards the
protected area and make certain that the view of the area is
unobstructed.
E.
Secure the detector in that position by tightening the locking screws on
the tilt mount. (Make sure the detector is in the correct position.)
The detector is now correctly located, aligned and ready to be connected
to the system.