Maintenance and Troubleshooting
FV-40 Series Flame Detector
087-0056 REV F
45
C.
Where dust, dirt or moisture accumulates on the window, first clean it
with a soft optical cloth and detergent, and then rinse with clean water
again.
D.
Inspect the detector for signs of damage, wear, or chemical attack, loose
fittings, corrosion or cracking. If evidence of damage is found, do not
use. Tag-out for repair. Failure to maintain proper operation of detector
may result in serious injury or death.
4.1.2 Periodic
Procedures
In addition to preventive cleaning and maintenance, the detector should be
functionally tested every six months or as dictated by local codes and
regulations. These tests should also be carried out if the detector has been
opened for any reason.
4.1.2.1 Power-Up
Procedure
Perform Power-Up procedure every time power is restored to the system.
Follow the instructions described in
Powering Up
.
4.1.2.2
Functional Test Procedure
Perform a functional test of the detector as described in
Internal Detector
Tests
.
4.1.3 Keeping
Maintenance
Records
It is recommended that maintenance operations performed on a detector
are recorded in a Log-book. The record should include the following:
Installation date, and contractor
Serial and tag no.
Entries for every maintenance operation performed, including the
description of the operation, date and personnel ID.
If a unit is sent to Scott Safety or a distributor for service, a copy of the
maintenance records should accompany it.
4.2 Troubleshooting
This section is intended to be a guide to correct problems which may happen
during normal operation.