Introduction
FV-40 Series Flame Detector
087-0056 REV F
15
This product is suitable to use in hazardous zones 1 and 2 with IIC gas group vapors
present, and zones 21 and 22 with IIIC dust type present.
1.4.5.2 FM, CSA
The FV-40 Series Flame Detectors are approved to FM Explosion Proof and
FM Functionality approved per FM3260:
Class I, Division 1, Groups B, C and D, T5 Ta = 85°C.
Dust Ignition Proof – Class II/III Division 1, Groups E, F and G.
Ingress Protection – IP67, IP66, NEMA 250 Type 6P.
Fuel Test Response including: Gasoline, N-Heptane, Diesel, JP5,
Kerosene, Ethyl, Alcohol 95%, IPA, Methanol, Methane, LPG,
Polypropylene, and Paper.
1.4.5.3 SIL-2 Approved (TÜV)
The FV-40 Series Flame Detector are pending to SIL-2 requirement per IEC
61508-4, Chapter 3.5.12.
The alert condition according to SIL-2 can be implemented by:
Alert signal via 0-20mA current loop.
or
Alert signal via alarm relay and fault relay.
For more details and guidelines for configuring, installing, operating, and
service, see
SIL-2 Features
on page 83 and TÜV Report No. 968/EZ
636.00/13.
1.4.5.4 EN54-10
The FV-40 Series Flame Detectors are pending to EN54-10 and CPD.
The detector has been tested and approved per EN54-10 by VdS
(Germany).
This test includes functional test, environmental test, EMI/EMC test and
software check.
1.4.5.5 INMETRO (UL)
The FV-40 Flame Detector is in compliance with the standards ABNT NBR
IEC 60079-0, ABNT NBR IEC 60079-1, ABNT NBR IEC 60079-7, ABNT
NBR IEC 60079-31 and INMETRO decree No. 179 as of May 18th, 2010.
Further details may be found on Certificate of Compliance No. UL-BR
16.0652X