Testing and Troubleshooting
Testing Methods and Tools
Test Methods
Test the pickup and dropout of relay elements using one of three methods:
➤
target command indication
➤
output contact closure
➤
sequential events recorder (SER)
The examples below show the settings necessary to route the phase time-
overcurrent element 51PT to the output contacts and the SER. The 51PT
element, like many in the SEL-351A, is controlled by enable settings and/or
torque control SEL
OGIC®
control equations. To enable the 51PT element, set
the E51P enable setting and 51PTC torque control settings to the following:
E51P =
1
(via the
SET
command)
51PTC =
1
(set directly to logical 1, via the
SET L
command)
Testing Via Target Commands
Display the state of relay elements, inputs, and outputs using the front-panel
or serial port
TAR
commands. Use this method to verify the pickup settings of
protection elements.
Testing With the Front-Panel TAR Command (only on models with LCD)
Access the front-panel
TAR
command from the front-panel
{OTHER}
pushbutton menu. To display the state of the 51PT element on the front-panel
display, press the
{OTHER}
pushbutton, cursor to the
TAR
option, and press
{SELECT}
. Press the
{Up Arrow}
pushbutton until
TAR 6
is displayed on the top
row of the LCD. The bottom row of the LCD displays all elements asserted in
Relay Word Row 6. The relay maps the state of the elements in Relay Word
Row 6 on the bottom row of LEDs. The 51PT element state is reflected on the
LED labeled
RS
for the correspondence between the Relay
Word elements and the
TAR
command.
Testing With the Serial Port TAR Command
To view the 51PT element status from the serial port, issue the
TAR 51PT
command. The relay will display the state of all elements in the Relay Word
row containing the 51PT element.
Review
TAR
and
Section 11: Front-Panel Interface
for further details on displaying element status
via the
TAR
commands.
Testing Via Output Contacts
You can set the relay to operate an output contact for testing a single element.
Use the
SET L
command (SEL
OGIC
control equations) to set an output
contact (e.g.,
OUT101
–
OUT107
) to the element under test. The available elements
are the Relay Word bits referenced in
Use this method especially for time testing time-overcurrent elements. For
example, to test the phase time-overcurrent element 51PT via output contact
OUT104
, make the following setting:
OUT104
=
51PT
Time-overcurrent curve and time-dial information can be found in
. Do not forget to reenter the correct relay settings when you
are finished testing and ready to place the relay in service.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...