10.22
SEL-351A Relay
Instruction Manual
Date Code 20080213
Serial Port Communications and Commands
Command Explanations
To view demand metering values, enter the command:
=>
MET D <Enter>
The output from an SEL-351A with wye-connected voltage inputs is shown:
=>
MET D <Enter>
FEEDER 1 Date: 08/10/99 Time: 15:08:05.615
STATION A
IA IB IC IN IG 3I2
DEMAND 188.6 186.6 191.8 0.2 4.5 4.7
PEAK 188.6 186.6 191.8 0.3 4.5 4.7
MWA MWB MWC MW3P MVARA MVARB MVARC MVAR3P
DEMAND IN 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
PEAK IN 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
DEMAND OUT 2.2 2.2 2.2 6.6 0.3 0.3 0.3 0.9
PEAK OUT 3.1 3.1 3.1 9.3 0.4 0.4 0.4 1.2
LAST DEMAND RESET 01/27/97 15:31:51.238 LAST PEAK RESET 01/27/97 15:31:56.239
=>
Reset the accumulated demand values using the
MET RD
command. Reset
the peak demand values using the
MET RP
command. For more information
on demand metering, see
MET E—Energy Metering
The
MET E
command displays the following quantities:
To view energy metering values, enter the command:
=>
MET E <Enter>
The output from an SEL-351A with wye-connected voltage inputs is shown:
=>
MET E <Enter>
FEEDER 1 Date: 08/10/99 Time: 15:11:24.056
STATION A
MWhA MWhB MWhC MWh3P MVARhA MVARhB MVARhC MVARh3P
IN 0.0 0.0 0.0 0.0 0.0 0.0 0.0 0.0
OUT 36.0 36.6 36.7 109.2 5.1 5.2 5.3 15.6
LAST RESET 01/31/97 23:31:28.864
=>
Reset the energy values using the
MET RE
command. For more information
on energy metering, see
.
MVAR
A,B,C
Single-phase megavars
(wye-connected voltage inputs only)
MVA
3P
Three-phase megavars
Reset Time Demand,
Peak
Last time the demands and peak demands
were reset
NOTE
for metering
behavior with small signals.
Energy MWh
A,B,C
Single-phase megawatt hours (in and out;
wye-connected voltage inputs only)
MWh
3P
Three-phase megawatt hours (in and out)
MVARh
A,B,C
Single-phase megavar hours (in and out;
wye-connected voltage inputs only)
MVARh
3P
Three-phase megavar hours (in and out)
Reset Time
Last time the energy meter was reset
NOTE
for metering
behavior with small signals.
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...