9.19
Date Code 20080213
Instruction Manual
SEL-351A Relay
Setting the Relay
Relay Word Bits (Used in SEL
OGIC
Control Equations)
5
50A
50A1 + 50A2 + 50A3 + 50A4 (see
50B
50B1 + 50B2 + 50B3 + 50B4 (see
50C
50C1 + 50C2 + 50C3 + 50C4 (see
51A
A-phase current above pickup setting 51AP for
A phase time-overcurrent element 51AT (see
Testing, Control
51AT
A-phase time-overcurrent element 51AT timed out (see
)
Tripping
51AR
A-phase time-overcurrent element 51AT reset (see
)
Testing
51B
B-phase current above pickup setting 51BP for B phase time-overcurrent
element 51BT (see
)
Testing, Control
51BT
B-phase time-overcurrent element 51BT timed out (see
)
Tripping
6
51BR
B-phase time-overcurrent element 51BT reset (see
)
Testing
51C
C-phase current above pickup setting 51CP for C phase time-overcurrent
element 51CT (see
)
Testing, Control
51CT
C-phase time-overcurrent element 51CT timed out (see
)
Tripping
51CR
C-phase time-overcurrent element 51CT reset (see
)
Testing
51P
Maximum phase current above pickup setting 51PP
for phase time-overcurrent element 51PT (see
Testing, Control
51PT
Phase time-overcurrent element 51PT timed out (see
)
Tripping
51PR
Phase time-overcurrent element 51PT reset (see
Testing
51N
Neutral-ground current (channel IN) above pickup setting 51NP
for neutral-ground time-overcurrent element 51NT (see
Testing, Control
7
51NT
Neutral-ground time-overcurrent element 51NT timed out
(see
Tripping
51NR
Neutral-ground time-overcurrent element 51NT reset (see
Testing
51G
Residual-ground current above pickup setting 51GP for residual-ground
time-overcurrent element 51GT (see
Testing, Control
51GT
Residual-ground time-overcurrent element 51GT timed out
(see
Tripping
51GR
Residual-ground time-overcurrent element 51GT reset (see
)
Testing
51Q1
a
Negative-sequence current above pickup setting 51QP for negative-
sequence time-overcurrent element 51QT (see
Testing, Control
51QT
Negative-sequence time-overcurrent element 51QT timed out
(see
Tripping
51QR
Negative-sequence time-overcurrent element 51QT reset
(see
Testing
Table 9.6
Relay Word Bit Definitions for SEL-351A
(Sheet 2 of 16)
Row
Bit
Definition
Primary Application
Summary of Contents for SEL-351A
Page 10: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 16: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 34: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 126: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 184: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 198: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 228: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 278: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 384: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 410: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 450: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 454: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 472: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 504: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 558: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 562: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 586: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 608: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...
Page 666: ...This page intentionally left blank Courtesy of NationalSwitchgear com ...