4.30
SEL-351-5, -6, -7 Relay
Instruction Manual
Date Code 20070117
Loss-of-Potential, Load Encroachment, and Directional Element Logic
Directional Control for Negative-Sequence and Phase Overcurrent Elements
Directional Control for Negative-Sequence and
Phase Overcurrent Elements
The directional control for overcurrent elements is enabled by making
directional control enable setting E32. Setting E32 and other directional
control settings are described in the following subsection
The negative-sequence voltage-polarized directional element controls the
negative-sequence overcurrent elements. Negative-sequence voltage-polarized
and positive-sequence voltage-polarized directional elements control the
phase overcurrent elements.
negative-sequence voltage-polarized and positive-sequence voltage-polarized
directional elements are enabled and routed to control the negative-sequence
and phase overcurrent elements.
If three-phase voltage signals are not available, make the group setting VNOM
= OFF. This prevents the negative-sequence voltage-polarized and positive-
sequence voltage-polarized elements from operating on false voltage
quantities, yet still allows the Best-Choice Ground Directional logic to operate
if available. This shut-down logic is shown in the center portions of
. See
Settings for Voltage Input Configuration on page 9.39
for
a complete list of changes caused by setting VNOM = OFF.
q
;
w
e
r
t
;
y
;
u
;
i
o
;
a
.
Figure 4.19
General Logic Flow of Directional Control for Negative-Sequence and Phase Overcurrent Elements
The negative-sequence voltage-polarized directional element has priority over
the positive-sequence voltage-polarized directional elements in controlling the
phase overcurrent elements. The negative-sequence voltage-polarized
directional element operates for unbalanced faults, while the positive-
sequence voltage-polarized directional element operates for three-phase
faults.
Internal Enables
and
.
The internal enable 32QE corresponds to the negative-sequence voltage-
polarized directional element.
F32P/
R32P
F32Q/
R32Q
q
y
32QE
(Disable)
50QF/
50QR
to Phase Time-
Overcurrent Elements
(
o
)
to Phase
Instantaneous/Definite
Time Overcurrent
Elements
(
a
)
Level 1
32PF/
32PR
Negative-
Sequence
Voltage-
Polarized
w
Positive-
Sequence
Voltage-
Polarized
e
r
32QF/
32QR
t
Level 1
Level 2
Level 3
Level 4
to Negative-Sequence
Instantaneous/Definite
Time Overcurrent
Elements
(
i
)
Level 2
Level 3
Level 4
to Negative-Sequence
Time-Overcurrent
Element (
u
)
Internal
Enables
Relay Word
Bit
Outputs
Relay Word
Bit
Outputs
Relay Word
Bit
Outputs
Directional
Elements
Direction
Forward/
Reverse Logic
Directional
Control
Directional
Element
Routing
Summary of Contents for SEL-351-5
Page 10: ...This page intentionally left blank ...
Page 22: ...This page intentionally left blank ...
Page 40: ...This page intentionally left blank ...
Page 80: ...This page intentionally left blank ...
Page 202: ...This page intentionally left blank ...
Page 238: ...This page intentionally left blank ...
Page 320: ...This page intentionally left blank ...
Page 402: ...This page intentionally left blank ...
Page 436: ...This page intentionally left blank ...
Page 478: ...This page intentionally left blank ...
Page 500: ...This page intentionally left blank ...
Page 594: ...This page intentionally left blank ...
Page 598: ...This page intentionally left blank ...
Page 622: ...This page intentionally left blank ...
Page 644: ...This page intentionally left blank ...
Page 674: ...This page intentionally left blank ...