Assembly and installation
02.00 | PW V6 | Assembly and operating manual | en | 389670
41
5.8 Set the product to its factory settings
The product can be set to its factory settings by the
DEFAULT
function.
Adapter board
2
Default
DIP switch
Factory settings/DEFAULT values
Reference value
Axis 1
Axis 2
Interface
RS232
RS232
Baud rate
9600
9600
Address
13
14
Ø
Disconnect the product from the power supply.
Ø
Unscrew the cover of the connection cap.
Ø
Switch
Default
DIP switch (2) to
ON
position.
Ø
Connect the product to the power supply.
Ø
Switch
Default
DIP switch (2) to
OFF
position.
Ø
Disconnect product from the power supply and reconnect
again.
Ø
Screw on the cover of the connection cap.
✔
The product is now reset to its factory settings.
5.9 Updating firmware
NOTICE
Risk of damaging the adapter board!
Faulty updating of the firmware can cause damage to the adapter
board.
•
Contact SCHUNK service.