Component Functions
EN-US · 30.30.01.02237 · 00 · 04/20
53 / 94
Data type
uint16
Length
32 bytes
Access
Read only
Value range
0 … 999
Default value
-
Unit
mbar
EEPROM
no
Vacuum Value of the Ejectors (0x0203)
This parameter is used to display the current vacuum in the individual ejectors.
Offset parame-
ter
515 (0x0203)
Description
System vacuum for ejectors
Index
Index 0 to 15 corresponds to ejector #1 to #16
Data type
uint16
Length
32 bytes
Access
Read only
Value range
0 … 999
Default value
-
Unit
mbar
EEPROM
no
Extended Ejector Data (0x2AF8 … 0x2B07)
Aggregated device data for each ejector can be displayed in these parameters. The individual values can
each be read separately via separate parameters (see above).
Offset parame-
ter
11000 (0x2AF8) … 11015 (0x2B07)
Description
Ejector extended values #1 … #16
Byte
1 ... 10
Data type
uint16
Length
10 bytes
Access
Read only
Value range
Byte 0:1: System vacuum (in mbar)
Byte 2:3: Air consumption (in l/min)
Byte 4:5: Leakage of last cycle (in mbar/s)
Byte 6:7: Evacuation time T1 (in ms)
Byte 8:9: Last free flow vacuum (in mbar)
Default value
-
Unit
EEPROM
no
6.3.2 Device Diagnostics
Device Status (Process Data) (0x000A)
The overall status of the ejector system is displayed as a status traffic light in “Process Data In.” All warn-
ings and errors are used to determine the status shown here.
This basic display provides immediate information about the status of the ejector with all its input and
output parameters.