OPERATING INSTRUCTIONS
19
CG700 rondo
Version: 27202 -
D
Schmalenberger GmbH + Co. KG
D-72072 Tübingen / Germany
Please observe:
•
The mains power connection must be a fixed connection.
•
Under no circumstances must there be any conducting connection between the metal
parts of the motor and the water.
•
The mains power supply cable must be equipped with an all-pole separator with a
contact opening of 3 mm.
•
At the marked connection terminal (at the foot of the motor or next to the terminal box)
an equalising potential with a cross-section of 10 mm² must be fitted.
5.2
Electrical connections AC
Protective measures:
fig. 29
Mains voltage:
230 V for 1 ~ AC
Mains power supply cable:
3 x 2.5 mm²
Pump connection cable:
3 x 2.5 mm²
Fuse:
16 A passive
B
=
Control unit in the pool
M
=
Motor of the circulation pump
N
=
Mains power supply
(230 V for 1~)
S
= Switchgear
cabinet
C
B
= Capacitor
Connection cable, for example,
HO7RNF, all further details required for
making connections can be found in
chapter 3.1.
fig. 30: Basic circuit diagram for 230 V
for 1 ~ AC
An earth leakage circuit breaker
(nominal fault current
≤
30 mA) must be
fitted to the mains power supply!
Important! Watch the order of the
terminal bridges!
See the inside of the terminal box lid or
enclosed circuit diagram. Please be sure
to observe instructions from the motor
manufacturer!
L
External conductor
N
Neutral conductor
8236
8464