Chapter 6
– Settings
Field B = Bus address of the DP slaves
SA represents the slave address. Here you set the bus
addresses of the DP slaves which are addressed via
transmission path.
Field C = Bus address of the DP master
MA represents the Master address. Here you set the bus
address of the PROFIBUS master.
Field D = Filter time
Enter addresses
The filter time is used to suppress short radio interferences.
Place the cursor into field A.
Select an unused table position (e.g. 01) by using the
buttons
< arrow up >
and
< arrow down >
to select a
value 01-04 or 01-07.
Place the cursor into field B.
Enter the desired DP slave address by using the
buttons
< arrow up >
and
< arrow down >
to select the
correct number. Use the buttons
< arrow right >
and
< arrow left >
to place the cursor below the correct
digit.
Unused table positions are represented by the value 127, i.e.
SA=127.
Press the button
<Enter>
if you would like to enter
further DP slave addresses.
The data will be saved and the cursor is placed below
the first digit in field A.
Repeat these steps for all further DP slaves.
Place the cursor in field C and enter the address of the
PROFIBUS master.
Assembly and commissioning instructions DATAEAGLE 3000